Emerson E2 Installation And Operation Manual page 97

For rx refrigeration, bx hvac, and cx convenience store controllers
Hide thumbs Also See for E2:
Table of Contents

Advertisement

P/N
Sensor
various
Temp Sensors
and Probes
various
Digital Sensors
(Klixons, Sail
Switches, etc.)
800-2100
Pressure Trans-
ducers (Emer-
800-2200
son Retail
800-2500
Solutions) 100,
200, 500 lb. rat-
ings
(0.5-4.5VDC
output, 5VDC
input voltage)
203-5750
Relative Humid-
ity Sensor
Table 9-1
- Sensor Wiring
The 16AI, 8IO, and MultiFlex Inputs
Input Type
Dip Switch
Up
1. Connect one lead to the odd
numbered terminal and the
other lead to the even num-
bered terminal (polarity
insensitive).
Up
1. Connect one lead to the odd numbered
terminal and the other lead to the even
numbered terminal (polarity insensitive).
Up
1. Connect RED power
wire to +5VDC sup-
ply on input board.
2. Connect WHITE sig-
nal wire to even num-
bered terminal.
3. Connect BLACK
ground wire to odd
numbered terminal.
4. Connect the bare
SHIELD wire to odd
numbered terminal.
Down
1. Wire the "P"
sensor terminal
to 12VDC sup-
ply on board.
2. Wire the
"GND" sensor
terminal to odd
numbered ter-
minal.
3. Wire the
"OUT" sensor
terminal to even
numbered ter-
minal.
4. Jumper sensor
terminal "N" to
sensor terminal
"GND".
Wiring
Input and Output Setup
-
9
3