Emerson E2 Installation And Operation Manual page 229

For rx refrigeration, bx hvac, and cx convenience store controllers
Hide thumbs Also See for E2:
Table of Contents

Advertisement

Alarm Name
Comb Temp Hi Limit Exceeded
Comb Temp Low Limit Exceeded User
Commission failed-chk network
Communication Port 1 Is Down
Communication Port 2 Is Down
Communication Port 3 Is Down
Communication Port 4 Is Down
Communication Port 6 is down
Completed Firmware Update
Config Loss - Chg In Tmpl Rev.
Config Loss-CRC Error
Config Loss-File CRC Error
Config Not Saved To Flash
Controller (or Device) Absent From
Network
Controller Reset
Controller Shutdown
Controller Startup
Default
Priority
User
The combined temperature of an entire Standard Cir-
cuit or Case Control Circuit has risen above its pro-
grammed high temperature setpoint.
The combined temperature of an entire Standard Cir-
cuit or Case Control Circuit has fallen below its pro-
grammed low temperature setpoint.
50
Commission of Echelon controller failed; binding of
NV was not successful. Check the Echelon network.
20
E2 cannot communicate with the RS232 port on the
E2 main board. The E2 main board likely needs
repair or replacement.
20
E2 cannot communicate with the RS485 network port
on the E2 main board. The E2 main board likely
needs repair or replacement.
20
E2 cannot communicate with the modem slot on the
E2. The E2 main board likely needs repair or replace-
ment.
20
COM4 is used by service personnel to attach hard-
ware used in test or debug functions. This alarm indi-
cates the port that allows E2 to communicate with
these devices is faulty. The E2 board likely needs
repair or replacement.
20
E2 cannot communicate with port 6 on the E2 main
board.
50
The E2's firmware was successfully updated.
15
Due to a difference between configuration templates
in a previous E2 version and templates in the current
version, configuration data could not be restored.
15
Due to an internal error, E2 has lost configuration
data.
15
Due to an internal error, E2 has lost configuration
data.
20
E2 could not save configuration data to flash mem-
ory.
20
The current E2 could not find the specified E2, I/O
board, or Echelon controller
50
An ARTC/MultiFlex RTU has gone through a reset.
50
The E2 has gone through a shutdown.
50
The E2 has re-started after a shutdown.
Definition
Appendix C: Alarm Advisory Messages
-
C
3