For rx refrigeration, bx hvac, and cx convenience store controllers
Hide thumbs Also See for E2:
Table of Contents

Advertisement

Alarm Name
Controller Type Mismatch
Controller Was Warm-booted
Couldn't Get File Handle
Curtail On
DFMC Standby Mode
DFMC Check Clock Settings
DFMC Over Max Defrost
DFMC Over Max Fan Delay
DFMC Inject Alarm
DFMC Door Alarm
Defrost terminated on Time
Defrost terminated on Temp.
Dest. Mem. Not Allocated Block
Dest. Mem. Out Of Stack Bounds
Device Absent From Network
Diagnostic Rate Change Failed
Dial To Day Time Site 1 Failed
C-4
E2 RX/BX/CX I&O Manual
Default
Priority
20
A device on the Echelon network is of a different
type than the user has specified. In other words, a
user might have wired a device such as a CC-100P to
the network but set it up in the E2 software as a CC-
100LS. Check your network setup and if necessary
reconfigure the device with the correct type.
50
A user has reset the E2 using the "reset" button on the
main board.
20
E2 tried to get a file from its memory and failed to do
so. This alarm likely indicates one or more templates
in the E2 software have been corrupted. Contact
Emerson Retail Solutions service for further assis-
tance.
User
A Curtailment device set up in Global Data has acti-
vated to begin curtail.
20
A DFMC is put into standby by a service technician;
it indicates the unit is not actually controlling.
99
Sent by the DFMC when it has lost its internal time-
of-day, E2 will resend the time upon receipt and this
alarm should return-to-normal without user interac-
tion.
20
A defrost duration was in excess of the maximum
limit defined. For example, the case is not defrosting
within spec.
30
Maximum fan delay time has been exceeded.
30
Related to the case's ability to get refrigerant into the
coil. For example, this alarm may occur if the case is
not being supplied with the proper temperature
refrigerant.
99
Door to a case has been left open too long.
30
EC2, EC3
30
EC2, EC3
50
An internal error has occurred in the E2.
50
An internal error has occurred in the E2.
20
The current E2 could not find the specified E2, I/O
board, or Echelon controller
20
A user tried to change the update rate of a CC-100,
RT-100, or similar Echelon device, but the change
was not accepted. Try the update rate change again. If
this alarm persists, call Emerson Retail Solutions ser-
vice.
20
E2 tried to dial out to the site listed as Day Time Site
1 and was unsuccessful.
Definition
026-1614 Rev 4 5-JAN-2013