Input Setup In E2; Configuring A Point From The Input Definitions/Status Screen - Emerson E2 Installation And Operation Manual

For rx refrigeration, bx hvac, and cx convenience store controllers
Hide thumbs Also See for E2:
Table of Contents

Advertisement

P/N
Sensor
550-2500
KW Transducer
550-2550
Table 9-1
- Sensor Wiring
9.1.3

Input Setup in E2

At this point in the setup process, you should have all
sensors, transducers, and other input devices wired to
points on MultiFlexes, 16AIs, and all output devices con-
nected to 8ROs, 8DOs, or 4AOs outputs. Once the physi-
cal wiring is complete, you will need to tell E2 the types of
sensors or devices that are connected to each I/O point.
This is achieved in the Input and Output Definitions
screens.
9.1.3.1
Configuring a Point from the
Input Definitions/Status Screen
To configure a point, go to the Input Definitions/Status
screen by pressing Alt + I or:
1.
Press
to open the Main Menu
2.
Press
(System Configuration)
3.
Press
(Input Definitions)
The Input Status screen opens:
9-6
E2 RX/BX/CX I&O Manual
Input Type
Dip Switch
Down for 4-
20mA, Up for
1. Wire positive transducer terminal
Pulse
to positive 24VDC supply.
2. Wire negative transducer termi-
nal to odd numbered input termi-
nal.
3. Wire negative 24VDC supply to
even numbered input terminal.
4. Place 250 resistor across odd
and even numbered input termi-
nals.
1. If the input board is an 8IO or a 16AI version
E.02 or greater, connect the two KWh terminals
to the input point (polarity insensitive)
2. If the input board is a 16AI version less than
E.02, connect the KWh terminals to board point
1. Set input switch #1 DOWN, and set input
switch #8 UP.
3. If the input board is a 16AIe, connect the two
KWh terminals to input # 1, 2, 3, or 4 ONLY.
Figure 9-4
the point you wish to set up, and press  (SETUP).
will prompt you to specify the point as analog or digital.
Press
Wiring
4-20 mA output to input board
Pulse Accumulator output to input board
- Input Status Screen
Use the up and down arrow keys to move the cursor to
A pop-up menu such as the one shown in Figure 9-5
if the input is analog, press
if the input is dig-
026-1614 Rev 4 5-JAN-2013

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents