No-Fuse Breakers, Fuses, Magnetic Contactors; Power Factor Improving Reactors - Mitsubishi Electric Melservo-J2-SUPER series Instruction Manual

General-purpose ac servo
Hide thumbs Also See for Melservo-J2-SUPER series:
Table of Contents

Advertisement

14. OPTIONS AND AUXILIARY EQUIPMENT

14.2.2 No-fuse breakers, fuses, magnetic contactors

Always use one no-fuse breaker and one magnetic contactor with one servo amplifier. When using a fuse
instead of the no-fuse breaker, use the one having the specifications given in this section.
Servo amplifier
MR-J2S-10CL (1)
MR-J2S-20CL
MR-J2S-40CL 20CL1
MR-J2S-60CL 40CL1
MR-J2S-70CL
MR-J2S-100CL
MR-J2S-200CL
MR-J2S-350CL
MR-J2S-500CL
MR-J2S-700CL

14.2.3 Power factor improving reactors

The input power factor is improved to be about 90%. For use with a 1-phase power supply, it may be
slightly lower than 90%.
W
RX S Y T Z
C
W1
Note. Connect a 1-phase 230VAC power supply to L
Servo amplifier
Model
MR-J2S-10CL(1)/20CL FR-BAL-0.4K
MR-J2S-40CL/20CL1
FR-BAL-0.75K
MR-J2S-60CL/ 70CL/
FR-BAL-1.5K
40CL1
MR-J2S-100CL
FR-BAL-2.2K
MR-J2S-200CL
FR-BAL-3.7K
MR-J2S-350CL
FR-BAL-7.5K
MR-J2S-500CL
FR-BAL-11K
MR-J2S-700CL
FR-BAL-15K
No-fuse breaker
Class
30 frame 5A
K5
30 frame 5A
K5
30 frame 10A
K5
30 frame 15A
K5
30 frame 15A
K5
30 frame 15A
K5
30 frame 20A
K5
30 frame 30A
K5
50 frame 50A
K5
100 frame 75A
K5
D1 5(0.2)
Installation screw
/L
and keep L
1
2
W
W1
135 (5.31) 120 (4.72) 115 (4.53)
135 (5.31) 120 (4.72) 115 (4.53)
160 (6.30) 145 (5.71) 140 (5.51)
160 (6.30) 145 (5.71) 140 (5.51)
220 (8.66) 200 (7.87) 192 (7.56)
220 (8.66) 200 (7.87) 194 (7.64) 120 (4.72) 100 (3.94)
280 (11.02) 255 (10.04) 220 (8.66) 135 (5.31) 100 (3.94) 12.5 (0.49)
295 (11.61) 270 (10.62) 275 (10.83) 133 (5.24) 110 (4.33) 12.5 (0.49)
Fuse
Magnetic contactor
Current [A]
Voltage [V]
10
10
15
20
20
250AC
25
40
70
125
150
[Unit : mm]
([Unit : in.])
3-phase
200 to 230VAC
1-phase
100 to 120VAC
open.
3
Dimensions [mm (in) ]
H
D
D1
59 (2.32)
45 (1.77)
69 (2.72)
57 (2.24)
71 (2.79)
55 (2.17)
91 (3.58)
75 (2.95)
90 (3.54)
70 (2.76)
14 - 32
S-N10
S-N18
S-N20
S-N35
S-N50
NFB
MC
FR-BAL
R
X
S
Y
T
Z
NFB
MC
FR-BAL
R
X
S
Y
T
Z
Mounting
Terminal
screw size
screw size
C
7.5 (0.29)
M4
M3.5
7.5 (0.29)
M4
M3.5
7.5 (0.29)
M4
M3.5
7.5 (0.29)
M4
M3.5
10 (0.39)
M5
10 (0.39)
M5
M6
M6
Servo amplifier
L
1
L
2
L
3
Servo amplifier
L
1
L
2
Weight
[kg (lb)]
2.0 (4.4)
2.8 (6.17)
3.7 (8.16)
5.6 (12.35)
M4
8.5 (18.74)
M5
14.5 (32.0)
M6
19 (41.9)
M6
27 (59.5)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents