Assembling The Inner Rails - HP StorageWorks 2/16 - SAN Switch Installation Manual

Hp storageworks san switch 2/16 v3.1.2 (aa-rr84d-te, may 2004)
Hide thumbs Also See for StorageWorks 2/16 - SAN Switch:
Table of Contents

Advertisement

Installing the SAN Switch 2/16
Note:
The mounting holes in the inner rails are marked 32, 16, and 8. When
mounting the SAN Switch 2/16, use the mounting holes labelled 16 to install the inner
rails on the switch.
When viewing a rack from the front, the left rails are used on the left side of the rack
and the right rails are used on the right side of the rack. The rails must match up—right
inner with right outer and left inner with left outer. Note that the SAN Switch mounts in
the rack with its front, the port side, facing the back of the rack. The rear of the switch,
the AC side, faces the front of the rack.
5. Assemble the two inner rails (one on each side) to the switch using ten of the
#8-32 x 5/16-inch Phillips pan-head SEMS screws as shown in
Figure
9.
Note:
The rail kit provides fourteen #8-32 x 5/16-inch screws for assembling the inner
rails. Each switch requires a different number of these screws. For example,
Figure 9
shows an inner rail being attached to the SAN Switch 2/16 with five screws. Attaching
both inner rails requires ten screws.
0012a
Figure 9: Assembling the inner rails
SAN Switch 2/16 Version 3.1.2 Installation Guide
33