To evaluate different modes of operation, data was recorded either with data
compression enabled or disabled. Thermocouples were affixed to key board
components as shown in
the tape path enclosure to monitor the approximate temperature of the media, as
shown in
Figure
4-4.
The results of the testing are listed in
Table 4-1. SDLT 220/320 Steady State Temperatures: Embedded Bezel
Component
1
HiFN
2
Hydra 1
3
Hydra 2
4
Coldfire
5
3.3-5.0 V Reg
6
Front Sensor
7
Rear Sensor
8
Headboard
9
Qlogic
10
Media Sensor
(Heads)
* The number in the Case Maximum Continuous Operating Temperature column are absolute limits that
should not be exceeded. In other words, expect physical component damage or failure if you exceed these
operating temperature limits by not providing adequate air flow through the drive.
Figure
4-2. In addition, a thermocouple was placed within
Table 4-1
10 degrees C
25 degrees C
Ambient
Ambient
Compression
Compression
2:1
2:1
On
Off
On
Temperature
Temperature
(degrees C)
(degrees C)
42.4
39.9
57.4
45.8
46.5
61.3
42.3
42.9
57.6
23.3
23.4
38.5
34.2
33.4
49.4
17.0
17.0
32.0
35.2
34.3
50.2
33.2
33.9
47.7
29.7
29.3
45.3
19.3
19.6
34.6
CHAPTER 4: Thermal Specifications
and
Table 4-2
below.
40 degrees C
Ambient
Compression
2:1
Off
On
Off
Temperature
(degrees C)
55.0
72.5
69.6
62.0
77.4
76.9
58.5
73.6
73.2
38.5
53.6
53.5
48.8
64.7
63.8
32.0
47.0
47.0
49.9
65.8
64.7
48.4
62.8
62.7
45.0
60.9
60.1
34.7
50.3
50.2
Case
Maximum *
Continuous
Operating
Temperature
(degrees C)
96
113
113
83
119
52
125
125
80
n/a