Control panel for fire detection and alarm, fire extinction and voice-evacuation systems
Hide thumbs Also See for PREVIDIA ULTRA:

Advertisement

Quick Links

Configuration manual
EN 54-2
EN 54-4
EN 54-16
EN 54-21
0051
EN 12094-1
22
0051-CPR-2741
0051-CPR-2826
0051-CPR-2827
CONTROL PANEL FOR FIRE DETECTION AND ALARM,
FIRE EXTINCTION AND VOICE-EVACUATION SYSTEMS
MANUAL FOR SYSTEM
CONFIGURATION, COMMISSIONING
AND MAINTENANCE
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PREVIDIA ULTRA and is the answer not in the manual?

Questions and answers

Summary of Contents for INIM Electronics PREVIDIA ULTRA

  • Page 1 EN 54-2 EN 54-4 Configuration manual EN 54-16 EN 54-21 0051 EN 12094-1 0051-CPR-2741 0051-CPR-2826 0051-CPR-2827 CONTROL PANEL FOR FIRE DETECTION AND ALARM, FIRE EXTINCTION AND VOICE-EVACUATION SYSTEMS MANUAL FOR SYSTEM CONFIGURATION, COMMISSIONING AND MAINTENANCE...
  • Page 2: Warranty

    In no case can INIM Electronics s.r.l. be held responsible or liable by the buyer or any other person for any loss or damage, direct or indirect, consequential or incidental.
  • Page 3: Table Of Contents

    Configuration manual Table of contents Warranty.......................... 2 Limited Warranty ......................2 Copyright........................2 Table of contents ......................3 Chapter 1 General information ....................5 Manufacturer's details ........................5 About this manual ..........................5 Description of the configuration and programming procedures ........6 Operator classification - Access Levels ..................6 Chapter 2 Configuring the fire detection system..............
  • Page 4 Fire detection and extinguishing systems Table of contents...
  • Page 5: Chapter 1 General Information

    About this manual Manual code: DCMCINE0PREVIDIAU Revision: 1.00 This manual describes the procedures for the configuration, commissioning and maintenance of the Previdia Ultra fire- detection system. 1.2.1 Terminology Control panel, System, Device: The main supervisory unit or any constituent part of the fire detection system.
  • Page 6: Description Of The Configuration And Programming Procedures

    Following is a flow chart which summarizes the operations to be carried out during the installation and commissioning phases of the Previdia Ultra system and indications regarding the manuals to refer to for each operation: Installation and cabling (refer to the Installation Manual) 2.
  • Page 7: Chapter 2 Configuring The Fire Detection System

    Chapter 2 Configuring the fire detection system Once the installation and cabling procedures have been completed (refer to the Installation Manual of the Previdia Ultra system) the system is ready for first startup. In the case of first start-up, the selection of the control panel languages is requested, a compulsory main language and an optional secondary language (see paragraph 4.5).
  • Page 8: Access To Programming

    If an Ethernet network connection is used, it will be necessary to set up the IP address and parameters of the network. This operation must be done for anyone of the following devices: • the Previdia Ultra control panel, via the main FPMCPU module • the backup FPMCPU module, via the FPMCPU module itself •...
  • Page 9: Modules Addressing

    Configuration manual Internal layout of the selected cabinet Internal module detected Position empty N.01 FW:1.0.0. Address and firmware revision of detected module N.01 FW:1.0.0. Modules assigned to N.01 FW:1.0.0. the fire detection and voice emergency N.04 FW:1.0.0. Network address: 2 system N.05 FW:1.0.0.
  • Page 10: Addressing The Repeaters

    Fire detection and extinguishing system Following is a table containing the addresses allowed for each type: Address Address Maximum Maximum FPM Module IFM Module number number from from FPMLED IFM24160 FPMLEDPRN IFM2L FPMEXT IFM4R IFM4IO IFMDIAL IFM16IO IFMNET IFMLAN IFMEXT Due to the fact that each FPMEXT front plate module is associated automatically with 5 internal IFMEXT modules at precise addresses, the FPMEXT modules must have an address which respects the IFMEXT - FPMEXT module association table which follows:...
  • Page 11: Enrolling Loop Devices (Ifm2L)

    Configuration manual Connection via RS485 BUS The BUS connection needs the addressing of any repeater in configuration, in order for the control panel to identify each module individually. To assign an address to a repeater, it is necessary to enter the configuration procedure Address starting from the display of the module itself, as described in the paragraph 2.3.
  • Page 12 Fire detection and extinguishing system operations necessary for the configuration of a single loop, however, it is implicit that the operations be repeated for each of the two loop. Loop Card Change Address Loop 1 Loop 2 Diagnostics Diagnostics Parameters Parameters Auto-configure Auto-configure...
  • Page 13 Configuration manual Section which provides data regarding the electrical status of the loop circuit: - Loop Status: indicates whether the loop is a closed ring circuit or open - Terminal Loop O: indicates eventual short-circuits or anomalies instantly on the “OUT” terminals - Terminal Loop I: indicates eventual short-circuits or anomalies instantly on the “IN”...
  • Page 14 Fire detection and extinguishing system Button to step back Configuring the fire detection system...
  • Page 15: Chapter 3 Configuration Of The Emergency Voice System

    Chapter 3 Configuration of the emergency voice system Once the installation and cabling procedures have been completed (refer to the Installation Manual of the Previdia Ultra system) the system is ready for first startup. In the case of first start-up, the selection of the control panel languages is requested (see paragraph 4.5).
  • Page 16: Access To Programming

    Fire detection and extinguishing system Access to programming In order to access the programming session of the voice emergency system, it is necessary to work through the following procedure: Insert the programming jumper on the back of the FPAMIAS module (see opposite, [A]).
  • Page 17: Modules Addressing

    Configuration manual Selection of one of the cabinets from the control panel layout ([G]) will show it both on the left ([A]), where the installed modules with their addresses and firmware revision are shown, and on the right ([I]), where the installed external modules with their network address are shown.
  • Page 18 Fire detection and extinguishing system Module layout Information on the 0 Line A Pagers Audio Matrix Line A Pagers module SN: SNSNSNSSN 26.1V FW: 1.1.1 Button to access the microphone bases of line A/B Information regarding the microphone bases of line A/B Button to access the messages saved to the flash memory...
  • Page 19: Configuration Of The Ifamfft Module

    Configuration manual • filtering algorithm for hands-free communications • volume Configuration of the IFAMFFT module The configuration of the IFAMFFT module is accessible through the main system configuration section of the emergency voice system (paragraph 3.2). The module can then be selected by tapping on the relevant icon in the section on the left, if the module is properly installed.
  • Page 20 Fire detection and extinguishing system Module layout Information on the module Button to access the Display Board settings SN: SNSNSNSSN FW: 1.1.1 Button to access the BUILD: bbbbbb PTT microphone configuration Button to access the TCP/IP settings Button to access the SD micro card functions Buttons for setting the...
  • Page 21: Configuration Of The Ifamamp Module

    The programming section of the voice-emergency control panel parameters via the FPMAMIAS module has, furthermore, an option that allows the operator to change the playback volumes of the voice and emergency messages without placing the Previdia Ultra control panel in programming status. The procedure to follow is described here.
  • Page 22 Fire detection and extinguishing system The section showing the following screen will open: Module layout Information on the module Button for addressing Audio Amplifier the module SN: SNSNSNSSN Address: 1 Button to access the settings Change Address Fan configuration button Audio Zone: Amplifier configuration button...
  • Page 23 The configuration of the logical groupings of the loudspeaker lines (audio zones and audio sectors) necessarily involves all the Previdia Ultra control panels connected to a network. In this case it is possible to program only via the software. In the case that the Previdia Ultra control panel is not connected to a network (network address equal to “0”), a programming section is available from the panel via the Modify button on the programming menu (paragraph 3.1).
  • Page 24 Fire detection and extinguishing system Configuration of the emergency voice system...
  • Page 25: Chapter 4 Generic Configuration Of The Control Panel

    Configuration manual Chapter 4 Generic configuration of the control panel This chapter describes the control panel configuration phases that can involve both the fire alarm system and the voice emergency system when both are present. Setting the network address (Hornet+ and IDANet) In the event that the installation involves more than one control panel connected to the network (through a Hornet+ connection or an IDANet connection, or both for the integration of the two systems), the network address must be set for each control panel.
  • Page 26: Acquiring The Configuration

    Fire detection and extinguishing system Information on the module Button for addressing the module Section containing a list of current faults Voltage and output current of the module PSU 1 Board Battery parameters Low battery voltage Output SN: SNSNSNSSN Missing mains 26.2 V (internal resistance, FW: 1.1.1...
  • Page 27: Signal Check And Fault Search

    Firmware revision The installer of Previdia Ultra system can see the firmware revision of each control panel module in order to facilitate any upgrade or configuration procedure. Such information can be achieved depending on the type of the module:...
  • Page 28: Registration Of The Control Panel To Inim Cloud

    Fire detection and extinguishing system Internal modules: the firmware of N.01 FW:1.0.0. each internal module (already installed) can be seen by accessing configuration menu (paragraph 2.3 - [J], paragraph 3.2 - N.01 FW:1.0.0. [K]). N.01 FW:1.0.0. N.04 FW:1.0.0. Network Address: 2 The address and the firmware N.05 FW:1.0.0.
  • Page 29: Chapter 5 Commissioning

    Configuration manual Chapter 5 Commissioning The commissioning phase is a set of tests and inspections which are necessary to ensure the full efficiency and proper functioning of the system as specified in the system project. This phase is essential and must be performed in a scrupulous way in accordance the regulatory requirements of the country where the system is installed and in full respect of the recommendations in the following section.
  • Page 30: Testing To Detectors And Manual Activations

    Fire detection and extinguishing system Testing to detectors and manual activations All the installed detectors must be tested during the commissioning phase. It is necessary to check the capacity of each detector to react to a simulated condition of fire, and to check the precision of the signals transmitted to the control panel in response to its activation (description of the point and zone).
  • Page 31 Configuration manual • Verification time (s), if an input device has the alarm verification option enabled, the maximum verification time is 30 minutes (EN 54-2 - clause 7.12.1 [c]). • Lock reset time after released (min), the maximum time is 30 minutes (EN 12094-1:2003 - clause 4.12.2). •...
  • Page 32: Chapter 6 Maintenance

    Fire detection and extinguishing system Chapter 6 Maintenance For correct and efficient management of the system it is necessary to carry out periodic maintenance in accordance with the regulatory requirements of the country where the system is installed and in full respect of the recommendations contained in this section.
  • Page 33 Configuration manual Maintenance...
  • Page 34 Fire detection and extinguishing system Maintenance...
  • Page 35 Configuration manual...
  • Page 36 Fire detection and extinguishing systems ISO 9001 Quality Management Certificate issued by BSI with number FM530352 Inim Electronics S.r.l. Centobuchi, via Dei Lavoratori 10 63076 Monteprandone (AP), Italy Tel. +39 0735 705007 _ Fax +39 0735 704912 info@inim.biz _ www.inim.biz...