• Verification time (s), if an input device has the alarm verification option enabled, the maximum verification time is 30
minutes (EN 54-2 - clause 7.12.1 [c]).
• Lock reset time after released (min), the maximum time is 30 minutes (EN 12094-1:2003 - clause 4.12.2).
• Pre-extinction time on automatic/manual activation, the maximum time is 60 seconds (EN 12094-1:2003 - clause
4.17.2).
• Valve ON time, the maximum time is 300 seconds (EN 12094-1:2003 - clause 4.21).
Refer to the Previdia/STUDIO software programming manual for more details about the parameters listed above.