Analog Output Units
5-2-3

Settings Using the Configurator

Setting the Output Range
and Output for
Communications Errors
The output range and the output for communications errors for the Analog
Output Unit can be set using version 1.11 or later of the DeviceNet Configura-
tor (referred to as the Configurator below). Using Ver. 1.20 or later, you can
also adjust or clear the offset and gain settings.
Use the following procedure to set the output range. The DeviceNet and the
MULTIPLE I/O TERMINAL must be connected first.
Note The output range can be set for each point using the Configurator.
Ranges can be set in 2-point units using DIP switches.
1,2,3...
1. Set pin 10 of the DIP switch for the Analog Output Unit to ON to set the
Software Setting Enable/Disable setting to enable.
2. Turn the power supply ON for all the Units of the MULTIPLE I/O TERMI-
NAL, including the Analog Unit and the Communications Unit.
3. Connect the Configurator to the DeviceNet network, making it online.
4. On the device list for the Configurator, double-click the Communications
Unit to which the Analog Output Unit is connected.
The Edit Device Parameters window for the Communications Unit that is
double-clicked, will be displayed.
Section 5-2
137