Gt1-Ad08Mx - Omron DEVICENET#05-2003 Operation Manual

Drt1-com gt1 series devicenet multiple i/o terminal
Table of Contents

Advertisement

Analog Input Units
5-1-2

GT1-AD08MX

106
General Specifications
Item
I/O connections
Number of inputs
Internal
Voltage range
power sup-
Current consump-
ply
tion in Unit (inrush
current)
Current consumption
(I/O Unit interface)
Noise immunity
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Operating atmosphere
Storage temperature
Safety standards
EMC directives
Mounting
Weight
Characteristics
Item
Input signal range
Max. signal input
Input impedance
Resolution
Accuracy
25 C
–10 C to
55 C
Conversion time
Converted output data
(Binary)
Averaging function
Open circuit detection
Dielectric strength
Isolation method
Connectors (made by MOLEX)
Either 8 points or 4 points (set with the DIP switch)
(Master Unit uses 8 input words or 4 input words.)
20.4 to 26.4 VDC (24 VDC
100 mA max.
(inrush current 30 A max.)
50 mA max.
2000 V
(IEC61000-4-4 via fast transient noise simulator)
10 to 150 Hz, 1.0-mm double amplitude or 70 m/s
2
200 m/s
–10 C to 55 C
25% to 85% (with no condensation)
No corrosive gases
–25 C to 65 C
UL508, CSA22.2
EN50081-2, EN50082-2
DIN 35-mm track
Approx. 180 g
Specification
Voltage inputs
0 to 5 V, 1 to 5 V, 0 to 10 V, or
–10 to 10 V
15 V
1 M min.
1/6000 (FS)
0.3% FS
0.6% FS
With 8 inputs: 8 ms/8 points
With 4 inputs: 4 ms/4 points
(Select using the DIP switch.)
Binary (4-digit hexadecimal)
–10- to 10-V range: F448 to 0 to 0BB8 full scale
Other signal ranges: 0000 to 1770 full scale
Settable (via DIP switch)
Provided. (with a range of 1 to 5 V or 4 to 20 mA)
500 VAC; detected current 1 mA (between communications
section and analog input, and between internal power sup-
ply and analog input)
Photocoupler insulation (between communications part and
analog input)
(no insulation between analog inputs)
Section 5-1
Specification
+10%
/
)
–15%
Current inputs
0 to 20 mA or 4 to 20 mA
30 mA
Approx. 250
0.4% FS
0.8% FS
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Drt1-comGt1Gt1-id16Gt1-od16mxGt1-ad08mxGt1-da04mx