Omron CX-INTEGRATOR - V2.3 REV 02-2009 Operation Manual page 108

Table of Contents

Advertisement

Field name on
Item
Network Tab Page
FINS Source
Network
Address
FINS Destination
Network
Address
Node
Frame
Length
Response
Timeout
Click the Driver Tab and set the following settings as required.
Set the IP address of the connected
Ethernet Unit.
2-2
Contents
Set the network address of the Ethernet network
connected to the computer.
Set the network address of the Ethernet network
connected to the PLC to which the connected
Ethernet Unit is mounted.
Set the node address of the connected Ethernet
Unit.
Set the node address set on the rotary switches
on the Ethernet Unit.
Set the maximum frame length.
Do not change the default setting.
This is the timeout time for receiving a response.
Increase this setting only if there are many
communications errors.
Select whether FINS node addresses are to be automatically generated
from IP addresses on the computer. This option is selected by default.
Clear this selection to enable using an IP address
table or combined method.
Set the computer's IP address according to the IP
address table.
Set the UDP port number.
Normally, the default value of 9600 is used.
Connecting Online to the Relay PLC
2-2-2
1 to 127
Use the default setting of 0
if there is only one Ethernet
Unit in the PLC and only
one network is being used.
1 to 127
Use the default setting of 0
if there is only one Ethernet
Unit in the PLC and only
one network is being used.
1 to 254
CS/CJ-series PLCs:
2,000 bytes
CVM1/CV-series PLCs:
1,950 bytes
2 s
Procedures
Settings
2-17