CX-Programmer Procedures
2. Select SYSMAC LINK Data Link Table and then click the OK button. The
Data Link Editor [SYSMAC LINK] will start.
3. Set the data link communications cycle time in the Cycle Time field under
Common Link. If you select Auto, the optimum communications cycle time
will be automatically calculated according to the data link tables. If you se-
lect Manual, set the time manually between 5 to 255 ms (refer to 4-11 Data
Link Characteristics for communications cycle time details).
4. Double click a node address in the Nodes field, or select Table and then
Edit Table Item. The Data Link Table Entry Dialog Box will appear.
Note (a) If using CX-Programmer Ver. 1.2 (Service Pack 1), select CV/
CVM1 for the PLC type when using a CS-series SYSMAC LINK
Unit.
If a CV/CVM1 PLC is set, the manual settings words will be limit-
ed to the same words as for CVM1/CV, as follows:
CIO Area: CIO 0000 to CIO 2555
DM Area: D00000 to D24575
(b) CS-series PLC types can be specified with CX-Programmer Ver.
2.0 or later and so the above limitations to manual settings words
do not apply.