Dm Area Allocations - Omron CS1W-SLK11-21 - 06-2004 Manual

Sysmac link units
Table of Contents

Advertisement

Software Switches (D30000 + 100 × Unit Number)
CPU Bus Unit Settings Initialization (See note)
0: Do not initialize CPU Bus Unit Settings
1: Initialize CPU Bus Unit Settings
Polling Node/Polled Node Bit
0: Polling node
1: Polled node
Note Initializes the network parameters registered in the CPU Bus Unit Setting Area in the CPU Unit and
clears the data link tables.
Appendix E

DM Area Allocations

Words in the DM Area are allocated to CS-series CPU Bus Units according to
the unit numbers assigned to them, as shown below. Each Unit is allocated
100 words, of which 1 word is used.
Unit No.
Words
0
D30000
1
D30100
2
D30200
3
D30300
4
D30400
5
D30500
6
D30600
7
D30700
Data Link Start Bit
Start: Changed from OFF to ON or already ON when power is turned ON
Stop: Changed from ON to OFF
Data Link Mode
00: Manual
01: Automatic for CIO Area only
10: Automatic for DM Area only
11: Automatic for CIO and DM Areas
Number of Send Words per Node
CIO Area
DM Area
00: 4 words
8 words
01: 8 words
16 words
10: 16 words
32 words
11: 32 words
64 words
Unit No.
Words
8
D30800
9
D30900
10
D31000
11
D31100
12
D31200
13
D31300
14
D31400
15
D31500
161