Omron CS1W-SLK11-21 - 06-2004 Manual page 146

Sysmac link units
Table of Contents

Advertisement

Troubleshooting
Indicators
RUN
ERC
ERH
Lit
---
Lit
Lit
---
---
Note
CPU Bus Unit CIO
Area error
INS
information
---
Bit 15 (error log infor-
mation) is ON.
Both bit 00 (network
parameter error) and
bit 15 (error log infor-
mation) are ON.
Both bit 01 (data link
table error) and bit 15
(error log informa-
tion) are ON.
Both bit 02 (routing
table error) and bit 15
(error log informa-
tion) are ON.
Not lit
---
---
---
---
---
Calculate the location of the error information in the CPU Bus Unit as follows:
CIO 1500 + unit number x 25 + 1 word.
Error
Probable cause
log
0001
CPU Unit error.
Hex
0012
CPU Bus Unit set-
Hex
tings area network
parameters data is
corrupted.
021A
Network parameter
Hex
settings contain an
error, or the local
node address
exceeds the network
parameters maxi-
mum node address.
0012
PLC Bus Unit system
Hex
settings area data link
tables data is cor-
rupted.
021A
The data link table
Hex
settings contain an
error.
0012
PLC parameter area
Hex
routing tables data is
corrupted.
021A
The routing table set-
Hex
tings contain an error.
---
Terminating resistors
are not mounted cor-
rectly (coaxial only).
---
The cable is not con-
nected correctly.
---
Node address
exceeds network
parameters maxi-
mum node address.
---
No other nodes exist. Be sure that there are a mini-
---
No node is set as the
polling node.
Section 8-1
Remedy
Refer to the PLC operation
manual, and clear the error. If
the error reoccurs, replace
the CPU Unit.
Correct the network parame-
ters. If the error reoccurs,
replace the PLC CPU Unit.
Correct the network parame-
ters correctly.
Correct the data link tables. If
the error reoccurs, replace
the PLC CPU Unit.
Correct the data link tables,
or delete the data link tables
if not using them.
Reset the routing tables. If
the error reoccurs, replace
the PLC CPU Unit.
Correct the routing tables, or
delete the routing tables if
not using them.
Mount terminating resistors
on both end nodes of the
SYSMAC LINK network.
Connect the cable connec-
tions, then reconnect the
cable correctly.
Either correct the network
parameters maximum node
address using CX-Net in CX-
Programmer, or set the node
address to within the maxi-
mum node address.
mum of two active nodes in
the network.
Set a Unit as the polling
node.
129