CX-Programmer Procedures
Settings and Display
Contents
74
7. The following display will appear when the data link table settings have
been made for all nodes. The example shows node 1 selected.
Item
Common
Cycle Time:
Link: Com-
Communications cycle
mon link
time
parameters
Target
Total link CH:
Node
Total number of
link words
Nodes
Node Information
Start Channel:
Start words
Refresh
Parameters
Contents
Data link communications cycle time:
Select automatic or manual settings. Man-
ual setting range: 5 to 255 ms.
Displays the total number of data link
words (CIO Area + DM Area). In the exam-
ple, CIO 70 words + DM 90 words = 160
words.
The number of send words is displayed for
each node. CIO: Number of CIO Area send
words. DM: Number of DM Area send
words. In the example, CIO: 20 send
words, DM: 30 send words.
Displays the words from which data links
start in the CIO and DM Areas for the
selected node. In the example, CIO 1000
and D00500 are displayed as the start
addresses.
Displays the order in which nodes are
refreshed in the second column from the
left. The values on the right are the number
of words received from the node in the CIO
Area and DM Area.
In this example, nodes are refreshed in the
order 1, 3, 2.