Cable Connections
Attaching Connectors to Coaxial Cable
2. Place an insulation cover over the F Adapter.
3. Any bends in the coaxial cable must be 45 mm in radius or greater (six
times the outer diameter of the cable). When laying the cable, make bends
of 110 mm in radius or greater (15 times the outer diameter of the cable).
Note
(1) Before connecting or removing the coaxial cable, always touch a ground-
ed metal object to discharge static electricity from your body.
(2) Always make sure the power is OFF before connecting the coaxial cable.
(3) Insert the coaxial connectors firmly. Also, be sure that the coaxial cable
is locked before use.
Assemble the connector parts as shown below.
Ferule
A hand crimp tool (CR-H-1130 by Dai-ichi Denshi Kogyo) is required when
crimping.
Insulation cover
Radius
45 mm minimum
Contact clip
Sleeve
Contact
Section 2-4
Body
Approx. 24.3 mm