Ac Input Cables; Ac Auxiliary Power Cable (3 Phase 480 V Ac); Ac Auxiliary Power Cable (1 Phase 120 V) - ABB HVC 200 Operation And Installation Manual

Table of Contents

Advertisement

12.13.2

AC input cables

Parameter
Cable shielding (optional)
Diameter of the phase conductors
Diameter of the PE conductor
Maximum diameter of the cable
conductor
Insulation
Ambient temperature range
Strip length
12.13.3

AC auxiliary power cable (3 phase 480 V AC)

Parameter
Type
Number of cores
Core identification
Cross section
Diameter
Conductor
Insulation
Nominal voltage
Test voltage
Ambient temperature range
Strip length
12.13.4

AC auxiliary power cable (1 phase 120 V)

Parameter
Type
Number of cores
Core identification
Cross section
Diameter
Conductor
Insulation
Nominal voltage
HVC 200/300/360-EN | 002
Specification
If the local rules require shielded cables, the
cable shielding must be connected to the PE
rail at both ends of the cable.
Refer to the local rules.
The same as the diameter of the phase con-
ductors
240 mm² (500 MCM AWG)
(Recommended)
Special PVC that is serviceable for outdoor
use, UV-protected, and oil resistant
-40 °C to +80 °C (-40 °F to +176 °F)
20 mm (0.75 in)
Specification
Unshielded
4
Acc. to IEC 60446
2.5 mm² (14 AWG)
5-10 mm (0.2-0.4 in)
Bare copper, fine wired, bunch stranded acc.
to VDE 0295 CI.5/IEC CI.5
Special PVC that is serviceable for outdoor
use, UV-protected, and oil resistant
0.6 KV / 1 kV
4 kV
-40 °C to +80 °C (-40 °F to +176 °F)
20 mm (0.78 in)
Specification
Unshielded
3
Acc. to IEC 60446
2.5 mm² (14 AWG)
6-12 mm (0.23-0.47 in)
Bare copper, fine wired, bunch stranded acc.
to VDE 0295 CI.5/IEC CI.5
Special PVC that is serviceable for outdoor
use, UV-protected, and oil resistant
0.45 kV / 0.75 kV
Technical data
83

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hvc 300Hvc 360

Table of Contents