Implementing thermal overload and short circuit
protections

Protecting the drive and input power cables in short-circuits

Cabinet-installed multidrives

To protect the input cable in short-circuit situations, install fuses or a suitable circuit
breaker at the supply side of the cabling.
The drive is equipped with fuses as standard. In case of a short-circuit inside the drive,
the fuses protect the drive, restrict drive damage, and prevent damage to adjoining
equipment.

Multidrive modules

To protect the input power cable in short-circuit situations, install fuses or a suitable
circuit breaker at the supply side of the cabling.
To protect the drive in short-circuit situations, install the ABB-specified fuses for the
supply unit, inverter units and other units. See the appropriate hardware manuals.
In additon, drive with ACS880-304LC...+A019 supply module: If you use parallel cables,
protect each cable against short-circuit individually. Obey the cabling and protection
instructions in ACS880-304LC...+A019 diode supply modules hardware manual
(3AXD50000045157 [English]).

Protecting the motor and motor cable in short-circuits

The drive protects the motor cable and motor in a short-circuit situation when:
the motor cable is sized correctly
the motor cable type complies with the motor cable selection guidelines by ABB
the cable length does not exceed the allowed maximum length specified for the
drive
the setting of parameter 99.10 Motor nominal power in the drive is equal with the
value given on the motor rating plate.
The electronic power output short-circuit protection circuitry meets the requirements
of IEC 60364-4-41 2005/AMD1.
Cable frame
Roxtec frame
S 8X4 AISI316
GHM 8X1 AISI316
GHM 8X1 AISI316
Electrical planning guidelines 37
Description
ABB designed flange and Roxtec frame
welded together.
Roxtec frame with integrated flange.
Roxtec 10mm wider than the roof
(410mm).
Roxtec frame with integrated flange.