Cable Specifications; General Specifications For Cables; Ac Input Cables; Auxiliary Ac Input Cables - ABB HVC-C 100-150 kW Installation Manual

Table of Contents

Advertisement

Technical data
20.12

Cable specifications

20.12.1

General specifications for cables

Parameter
Ambient resistance
Compliance
Isolation requirements
20.12.2

AC input cables

Parameter
Cable shielding (optional)
Diameter of the phase conductors
Diameter of the PE conductor
Maximum diameter of the cable
conductor
Strip length
20.12.3

Auxiliary AC input cables

Parameter
Cable shielding (optional)
Diameter of the phase conductors
Diameter of the PE conductor
Maximum diameter of the cable conduc-
tor
Strip length
20.12.4

DC power cables

Parameter
Type
Number of cores
Cross section range (minimum)
98
Specification
Resistance to placing in the ground, sub-
merged in conduit
Compliance with the VDE, CE, EAC Low Volt-
age Directive and the RoHS compliance.
Self-extinguishing and flame retardant isola-
tion according to DIN VDE 0482-332-1-2, DIN
EN 60332-1-2, IEC 60332-1-2
Specification
If the local rules require shielded cables, the
cable shielding must be connected to the PE
rail at both ends of the cable.
Refer to the local rules.
The same as the diameter of the phase con-
ductors
240 mm²
20 mm
Specification
If the local rules require shielded cables,
the cable shielding must be connected
to the PE rail at both ends of the cable.
Refer to the local rules.
The same as the diameter of the phase
conductors
240 mm²
20 mm
Specification
1x positive, 1x negative cable
Unshielded
1
95 mm²
6AGA000007-0611-EN | 001