7.8.2
Torque command / torque limit via PROFIBUS communication (Pr.804) (only for
the FR-A800 series)
Setting Pr.804 Torque command source selection = "3 or 5" enables torque command / torque limit via PROFIBUS
communication under Real sensorless vector control, torque control under vector control, and speed control.
(When Pr.804  "3 or 5", writing a torque command/limit value via PROFIBUS communication causes turning ON of Alarm 1 to
Alarm 7 corresponding to REF1 to REF7, resulting in generation of a command execution error.)
Initial
Pr.
Name
value
Torque
command
804
0
source
selection
*1
Can also be set from operation panel or parameter unit.
*2
When used as a torque limit value, the value is an absolute value.
*3
The priority of the torque limit value is as follows: TL signal > PROFIBUS communication > Pr.810.
Setting
range
(used under torque control)
0
Torque command by terminal 1 analog input
Torque command by the parameter setting (Pr.805 or Pr.806)
1
*1
(-400% to 400%)
Torque command via PROFIBUS communication (FR-A8NP)
• Torque command by the parameter setting (Pr.805 or Pr.806)
*1
3
(-400% to 400%)
• Setting is available in the buffer memory REF1 to REF7
(-400% to 400%)
4
16-bit digital input (FR-A8AX)
Torque command via PROFIBUS communication (FR-A8NP)
• Torque command by the parameter setting (Pr.805 or Pr.806)
5
(-327.68% to 327.67%)
• Setting is available in the buffer memory REF1 to REF7
(-327.68% to 327.67%)
Torque command by the parameter setting (Pr.805 or Pr.806)
6
(-327.68% to 327.67%)
Torque command
*1
*1
PPO TYPE SUPPORT SPECIFICATION
Torque limit
*2
(used under speed control)
Input via PROFIBUS
communication is not available.
Input via PROFIBUS
communication is available.
(Regardless of the priority of the
*3
torque limit value input
)
Input via PROFIBUS
communication is not available.
Input via PROFIBUS
communication is available.
(Regardless of the priority of the
*3
torque limit value input
)
Input via PROFIBUS
communication is not available.
75
7