Inverter status/operation command
The inverter status can be monitored and operation command can be given from the master.
IND
PNU
H0100
HA
*1
Signal names are initial values. Using Pr.180 to Pr.187, you can change input signal functions. Refer to the Instruction Manual (Detailed)
of the inverter for details of Pr.180 to Pr.187.
*2
For the FR-F800 series, no function is assigned in the initial setting.
Operation mode read/write
Read/write of the operation mode can be performed from the master.
IND
PNU
H0100
HB
88
PPO TYPE NON-SUPPORT SPECIFICATION
Inverter status
For details, refer to ZSW on
page
Run command
Functions assigned to terminals RH, RM, RL, JOG, RT, AU, CS and MRS are activated.
Bit 0: Not used (0 is set)
Bit 1: Terminal STF (Forward rotation command)
Bit 2: Terminal STR (Reverse rotation command)
Bit 3: Terminal RH (High-speed operation command
Bit 4: Terminal RM (Middle-speed operation command
Bit 5: Terminal RL (Low-speed operation command
Bit 6: Terminal JOG (JOG operation selection
Bit 7: Terminal RT (Second function selection
Bit 8: Terminal AU (Terminal 4 input selection
Bit 9: Terminal CS (Restart after instantaneous power failure selection
Bit 10: Terminal MRS (Inverter output shut off
Bit11 to 15: Not used (0 is set)
Item
Operation mode
Item
84.
*1
)
*1
)
*1
)
*1
)
*1
)
*1
)
*1
)
External operation mode: H10
PU operation mode: H11 (When Pr.79 = "6")
Network operation mode: H14
*1*2
)
Data definition