Mitsubishi Electric 800 Series Instruction Manual page 55

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

PZD
Name
Control enable
Fault reset
(Reset)
(Standard format)
STW
REF1 enable
(Extended format)
PZD enable
STF signal
STR signal
Terminal RT function
MRS signal
RAM/EEPROM
54
PPO TYPE SUPPORT SPECIFICATION
Bit
0 to 2
Not used (1 is set)
3
0: Inverter output shutoff, 1: Inverter output shutoff is cancelled
4 to 6
Not used (1 is set)
[At inverter error]
0: No action
1: Fault reset (Reset).
7
The operation depends on the Pr.349 setting. (Refer to
[When inverter is normal]
No action
8
Not used (0 is set)
9
Not used (0 is set)
*1
9
0: REF1 disabled, 1: REF1 enabled (The REF1 setting is applied to the inverter.)
0: Command request of PZD is not processed.
10
1: Command request of PZD is processed.
At power-on or inverter reset, set 1 once.
11
0: OFF, 1: ON (forward rotation command)
12
0: OFF, 1: ON (reverse rotation command)
13
Second function selection
14
0: OFF, 1: ON (output is shut off)
0: Set frequency (HSW) is written to RAM (Power-on reset returns the changed
15
set frequency to the setting before it was written to RAM.).
1: Set frequency (HSW) is written to EEPROM.
Definition
page
*2
The function assigned to terminal RT is
*5
activated.
35.)