Design Guide | VLT® AutomationDrive FC 360
Table 65: Status Word According to FC Profile (continued)
Bit
07
08
09
10
11
12
13
14
15
Explanation of the status bits
Bit 00, Control not ready/ready
Bit 00=0: The drive trips.
Bit 00=1: The drive controls are ready but the power component does not necessarily receive any supply (if there is 24 V external supply
to controls).
Bit 01, Drive ready
Bit 01=0: The drive is not ready.
Bit 01=1: The drive is ready for operation, but the coasting command is active via the digital inputs or via serial communication.
Bit 02, Coast stop
Bit 02=0: The drive releases the motor.
Bit 02=1: The drive starts the motor with a start command.
Bit 03, No error/trip
Bit 03=0: The drive is not in fault mode.
Bit 03=1: The drive trips. To re-establish operation, press [Reset].
Bit 04, No error/error (no trip)
Bit 04=0: The drive is not in fault mode.
Bit 04=1: The drive shows an error but does not trip.
Bit 05, Not used
Bit 05 is not used in the status word.
Bit 06, No error/triplock
Bit 06=0: The drive is not in fault mode.
Bit 06=1: The drive is tripped and locked.
Bit 07, No warning/warning
Danfoss A/S © 2024.01
Bit value=0
No warning
Speed≠reference
Local operation
Out of frequency limit
No operation
Drive OK
Voltage OK
Torque OK
Timer OK
Bit value=1
Warning
Speed=reference
Bus control
Frequency limit OK
In operation
Stopped, auto start
Voltage exceeded
Torque exceeded
Timer exceeded
AJ435824192086en-000101 / 130R1295 |
117