Chapter V Usage Description

5.1. Power Consumption Calculation Example

For coupler module, here, take ZMIO310-ECAT communication module as the
example.
External ECAT communication module is supplied by DC24V, internal coupler
supplies 5V power for each module, the max output current is 2A. Except itself internal
power consumption 1.6W, and it supplies 8.4W power for each expansion submodule.
Please see below form for reference.
Model
ZMIO310-ECAT
ZMIO310-16DI
ZMIO310-16DO
ZMIO310-16DOP
ZMIO310-4AD
ZMIO310-4DA

5.2. IO Starting Number Configuration

5.2.1. EtherCAT Bus Expansion

If coupler uses ECAT communication module, IO starting numbers of IN input module
and DO/DOP output modules are configured through "NODE_IO" command, AIO starting
numbers of AD module and DA module are configured through "NODE_AIO" command.
Grammar
Parameters
ZMIO310 Vertical Bus Expansion Module User Manual V1.0
ECAT communication module 1.6W
...
NODE_IO
NODE_IO (slot, node) = iobase
slot
Controller bus slot No.
node
Device No.
Description
Input module 0.3W
Output module (NPN) 0.3W
Output module (PNP) 0.3W
AD module 0.4W
DA module 0.3W
...
Default is 0