Zmotion ZMIO300-4AD Manual
Hide thumbs Also See for ZMIO300-4AD:

Advertisement

Quick Links

ZMIO300-4AD / DAExpansion submodule
 1 Introduction
ZMIO300-4AD/ DAThe expansion submodule is used by the ZMIO300 expansion
module4Channel analog input / output expansion module. When AWhen IO resources are
not enough,It can be used with ZMIO300-ECAT communication module to expand the
number of analog input / output ports.
This manual mainly describes 4AD/ DAThe specifications, characteristics, and usage
methods of the expansion submodule are convenient for reference. Please read this
manual in detail before use in order to grasp the characteristics of the product more clearly
and use the product more safely.
 2. Copyright notice
The copyright of this manual belongs to Shenzhen Zhengshen Technology Co., Ltd.
Without the written permission of Zhengshen, no one can reprint, translate and copy any
content in this manual.
Refer to the "ZBASIC Software Manual" for details of the user-developed software
related to the controller of this product and the introduction and routines of each
instruction.
The information in this manual is for reference only. Due to the improvement of design
and function, Zhengshang Technology Co., Ltd. reserves the right of final interpretation of
this document! The content is subject to change without notice!
Please refer to the website of Zhengshen Technology Company (www.zmotion.com.cn)
The latest release shall prevail.
 3. Safety precautions
Safety precautions are divided into two levels: "danger" and "caution". Please operate
correctly under the premise of paying full attention to safety.
Danger: Failure to follow the instructions may result in death or serious injury!
ZMIO300-4AD/ DAExpansion submodule hardware manual Version 1.1
consequences. Observe the instructions for both levelsOtherwise, it may result in death or
serious injury, and damage to this product, related machines and systems. Zhengshang
Technology Company has no obligation or responsibility for this.
manual to the end user.
Danger
note
Note: Failure to operate as required may result in moderate or minor injuries and
equipment damage.
Depending on the situation, even if "note"Matters at this level may also have serious
Please keep this guide in a safe place for future reading, and be sure to give this
installation
The person installing this product must be trained in knowledge of
electrical equipment;
When the expansion module is disassembled, the external power supply
used by the system is all disconnected before operation, otherwise it may
cause equipment misoperation or damage the equipment;
Please prohibit the use in the following occasions:Locations with dust,
oily smoke, conductive dust, corrosive gas, and flammable gas.Exposure
to high temperature, condensation, wind and rain.Occasions with
vibration and shock.electric shock,Fire and misuse can also cause
product damage and deterioration.
During installation, avoid metal chips and wire ends falling into the
ventilation holes of the expansion sub-module, which may cause fire,
failure, and misoperation;
After installation, ensure that there are no foreign objects on the
ventilation surface, otherwise it may cause poor heat dissipation,
causing fire, failure, and misoperation;
When installing, they should be tightly connected to their respective
connectors, and the module connection hooks should be firmly locked. If
the module is improperly installed, it may cause malfunctions,
malfunctions and fall-off.
Wiring

Advertisement

Table of Contents
loading

Summary of Contents for Zmotion ZMIO300-4AD

  • Page 1 Zhengshang Technology Company has no obligation or responsibility for this. ZMIO300-4AD/ DAThe expansion submodule is used by the ZMIO300 expansion Please keep this guide in a safe place for future reading, and be sure to give this module4Channel analog input / output expansion module.
  • Page 2: Nameplate Information

    ZMIO300-4AD/ DAExpansion submodule hardware manual Version 1.1 The person who conducts the wiring of this product must be trained in Nameplate information  the knowledge of electrical equipment; When wiring, the external power supply used by the system must be disconnected before operation.
  • Page 3 ZMIO300-4AD/ DAExpansion submodule hardware manual Version 1.1 Status Status userInput User localExte localExte nded nded localExte localExte nded nded Outside 24V Outside 24V power power figure 2 4AD expansion submodule interface diagram Numbering Interface name Function Description image 3 4DASchematic diagram of the expansion submodule interface...
  • Page 4: Performance Specifications

    0 ~ 55 ℃) Installation dimensions  Limit voltage ± 12V Limit current Instantaneous ± 30mA, average ± 24mA ZMIO300-4AD/ DABoth models have the same size, the installation dimension drawing is ZMIO300-4ADexample. Internal power 0.4W consumption Power consumption 0.7W I/ OBetween terminals and sub-module power: isolation;...
  • Page 5: Terminal Definition

    ZMIO300-4AD/ DAExpansion submodule hardware manual Version 1.1 installation steps: number Please use the standard 35mm DIN rail. Input Channel 0 I+ Open the gap snap of the expansion submodule, align the local expansion front- Input Channel 0 V+ level interface of the expansion submodule with the local expansion rear-level...
  • Page 6 ZMIO300-4AD/ DAExpansion submodule hardware manual Version 1.1 Set aside coupler supplies 5V to each module, and the maximum output is 2A. In addition to the 1.6W internal power consumption of the ECAT communication module itself, it can also provide Output Channel 2 I+ 8.4W to each expansion sub-module.
  • Page 7: Wiring Precautions

    ZMIO300-4AD/ DAExpansion submodule hardware manual Version 1.1 numbers are the same, the two will work at the same time, it is not Wiring precautions  recommended to do so. When wiring terminal wiring, avoid binding with cables with strong interference Address description ...
  • Page 8: Configuration Function

    ZMIO300-4AD/ DAExpansion submodule hardware manual Version 1.1 SLOT_SCAN (0) 'Bus scan By using input and output related instructions AIN, AOUT operationAD/ DA.Since ? RETURN 'Scan successfully returned -1 4AD,4The resolution of the DA expansion sub-module is 16 bits, and the scale value of the AIN and AOUT commands ranges from 0 to 65535.
  • Page 9 ZMIO300-4AD/ DAExpansion submodule hardware manual Version 1.1 SDO_WRITE (0,0, $ 5001,2,6,12) 'Channels 2 and 3 open name SDO_WRITE (0,0, $ 5001,2,6,15) 'All channels are on Function This function is used to switchThe range of the input or output channel of Description the AD or DA expansion submodule;...
  • Page 10: Configuration Considerations

    ZMIO300-4AD/ DAExpansion submodule hardware manual Version 1.1 example second is DA expansion submodule SDO_WRITE (0,0, $ 5001,1,6,3) 'The range expansion submodule is switched to -10 ~ 10V SDO_WRITE (0,0, $ 5001,1,6,5) 'The range expansion submodule is switched to 0 ~ 20mA...
  • Page 11 ZMIO300-4AD/ DAExpansion submodule hardware manual Version 1.1  8. Data dictionary description Description format  Subindex Authorit Index (hex) Object name Default value data range unit type of data (hex) index(hex): The index number of the object, represented by a four-digit hexadecimal number. Sub-index (hex): The sub-index number of the object, represented by a two- digit hexadecimal number.
  • Page 12 ZMIO300-4AD/ DAExpansion submodule hardware manual Version 1.1 write *1. The meaning of the setting value of sub-index 1 is as follows Set value meaning 0 ~ 10V -10 ~ 10V 4 ~ 20mA 0 ~ 20mA 0 ~ 5V -5 ~ 5V -20 ~ 20mA *2.
  • Page 13 ZMIO300-4AD/ DAExpansion submodule hardware manual Version 1.1 Read / OUT_GEN_INT4 0x0000 to 0xFFFF UNSIGNED16 write 5000+Extension Read CONFIG_DATA UNSIGNED8 submodule address only Read / CONFIG_1_INDENT 10 to 15*1 UNSIGNED16 write Read / CONFIG_2_INDENT UNSIGNED16 write *1. The meaning of the setting value of sub-index 1 is as follows...

Table of Contents