This function is valid for current AD module.

6.4.4. Range-Switch Configuration

Function description
Object to use
Data dictionary
Examples
Type number description:
Type No.
1
2
3
4
ZMIO310 Vertical Bus Expansion Module User Manual V1.0
SDO_WRITE(0,0,$5006,2,6,12)
SDO_WRITE(0,0,$5006,2,6,15)
This function is used to switch the range of the input channel
of the AD module (or the output channel of the DA module), and
the default value of both modules is the range of 0~10V
The measuring range corresponds to the type number of the
expansion sub-module, please refer to the table below.
Analog input module: ZMIO310-4AD.
Analog output module: ZMIO310-4DA.
5007h, 5006h: 5001h + extension No. of the corresponding AD
module or DA module, please refer to Chapter 6.4.1 for sub-
module address assignment.
'5007h is the DA module control dictionary, 5006h is the AD
module control dictionary.
SDO_WRITE(0,0,$5006,1,6,3)
'AD module is switched to -10~10V range
SDO_WRITE(0,0,$5006,1,6,5)
'AD module is switched to 0~20mA range
SDO_WRITE(0,0,$5007,1,6,11)
'DA module is switched to -10~10V range
SDO_WRITE(0,0,$5007,1,6,13)
'DA module is switched to 0~20mA range
Type name
Module type
ZM1111
Input module
ZM1112
ZM1113
ZM1114
'channel 2, 3 are ON.
'full channels are ON.
Corresponding range
AD module
AD module
AD module
--
0~10V
-10~10V
4~20mA