Type of input
Voltage input method (power supplied
by IO)
Current (input)(typical)
Impedance (input)
Frequency (input)
Action showing (input)
Voltage when ON
Voltage when OFF
Internal Power
Power
Isolation

4.1.3. Installation Size

→ Installation Step:
Please use 35mm standard DIN guide rail.
Open guide rail buckle of input module, then embed input module in the DIN guide
rail.
Press fit guide rail buckle of input module, then fix input module in the DIN guide rail.
ZMIO310 Vertical Bus Expansion Module User Manual V1.0
Digital input
PNP (COM1 is connected to 24V power -, COM2 is
connected to 24V power +) or NPN (COM1 is connected to
24V power +, COM2 is connected to 24V power -)
NPN type (-4.8mA), PNP type (+4.8mA)
When input is ON, the input indication led will be ON.
PNP Type >7.2V or NPN type <14.5V
PNP Type >6.8V or NPN type <14.7V
Optocoupler isolation
4.7KΩ
<5kHz
0.3W
1.9W