Characteristic and setting
2.19.2
The hatched area of Figure 2.19-2 illustrates the BCD characteristic; the BCD function will
operate when the positive sequence current (I1) is larger than 0.04×In, the negative sequence
current (I2) is larger than 0.01×In, and the ratio |I
I
2
0.01×In
o
0.04×In
Miscellaneous functions
2.19.3
Harmonic detection function
(i)
The operation of BCD can be blocked when the IED detects 2
phenomenon of magnetizing inrush current when a transformer is energized. To block the
operation of the BCD function during the occurrence of the harmonic, set scheme switch [BCD-
2fBlk] Block.
Block operation of CTF for BCD
(ii)
The operation of the BCD function can be blocked by the current transformer failure (CTF)
function using a scheme switch. Block is set for scheme switch [BCD-CTFBlk] if the user wishes
to disable the operation of the BCD function when a current transformer failure occurs.
| ��
2
| ��
| ≥ 0.04 × ����
1
| ��
| ≥ 0.01 × ����
2
Figure 2.19-2 Characteristic of BCD
- 288 -
/I
| is higher than setting [BCD].
2
1
|
≥ ������ ��������������
| ��
|
1
I
1
nd
6F2S1914 (0.49)
BCD
&
harmonic caused by the
GRL200 (Soft 033 & 037)