Data communication interface
2.36.1
Communication interface is relevant to the property and capacity of channels; hence, IEEE
C37.94 (either N=1 or N=3) is provided in the DIF_COMM function. Securing clock recovery,
jitter tolerance, physical connection, and spuriousness are specified by the international
standard.
IEEE C37.94 (N=1)
(i)
The C37.94 (N=1) link provides transmission format. Thereby, the DIF_COMM function uses
the transmission format for sending. The data which is sent for the remote-terminal is current
values, command signals and others:
Current data in phase–a, –b, and –c at sampling time
Residual current data at sampling time
Output signals in phase-a, -b, and –c from the differential protection function
Statuses of breaker and disconnector in phase–a, –b, and –c
Statuses of scheme switches such as test and others
Blocking commands for reclosing
Sampling synchronization control signals
Synchronized test trigger signals
User configurable data
The current data are represented in instantaneous values; the values are sampled every
30-electrical degree. For instance, provided the power system frequency is 60 Hz, the 30-
electrical degree means that the sampling interval is 1.38 milliseconds (=1/720Hz). Twelve bits
(11 data bits plus a sign bit) are used to present a current data. The IED determines the current
data in the every 30-electrical degree; hence the DIF_COMM function can send the data in the
every 30-electrical degree. The DIF_COMM function also sends commands and other data; the
data are made of several signals: a signal of the differential current function, a signal of the
direct transfer trip function, a test signal, and a sync signal. Note that the DIF_COMM
function sends a signal per the 30-electrical degree with regard to the differential current
function the direct the transfer trip function. On the other hand, the DIF_COMM function
sends the other signals per 360-electrcal degree (=a cycle of the power system frequency)
The transmission format includes cyclic redundancy check (CRC) bits and check bit solid.
In case of communication failure, the DIF_COMM function set zero data for the format so as
not to operate the differential and other protection functions. Consequently, the protection
function corresponding to the DIF_COMM function can halt.
When the user wishes to use a communication module for the protection in the IEEE
C37.94 (N=1) at the channel#1, set Normal for the scheme switch [CH1_COM_WIDTH], for