Setting for the operation
2.11.1
To the operation, the user should set On for scheme switch [DTT*-EN]; then, the user should
set for the scheme switch [DTT*-Output] to select an mode when the DTT function receives a
command from the remote terminal. The user should set TRIP for the scheme switch [DTT*-
Output] when tripping the CB
Output] when tripping the CB is not required but issuing an alarm is required using the binary
output circuit
.
2
To delay for issuing the trip signal, the user can set the delay time using [TDTT*] among
0.00 to 300.00sec.
If the operation of the autoreclose (ARC
function receives a signal from the remote end, set Block for scheme switch [DTT*-ARCBlk].
Note: Issuing the trip command is performed in trip circuit (TRC). For more
1
information, see chapter
Note: For programing binary output circuits, see chapter
2
IO module
Note: ARC is discussed separately. See chapter
3
is required. Conversely, set BO for the scheme switch [DTT*-
1
Relay application: Trip circuit
.
- 181 -
) function must be blocked when the DTT
3
, separately.
Technical description: Binary
Relay application: Autoreclose