Command for tripping CB and signal to block reclosing CB#1/CB#2
2.33.1
The TRC logic is designed to issue per-phase trip or three-phase trip commands when a fault
occurs. Table 2.33-2 shows the receipt of trip signals from the protection functions, which are
identified by 'Protection function identification numbers ('
signal for the ARC function is also provided along with the trip signal.
Table 2.33-2 Trip/ARC block signal inputs to the TRC function
Protection
ID
FC*_OPT
'*'
functions
_TRIP-A
DIFL
1
DIFGL
2
OSTV
3
DTT
4
N.A.
5
N.A.
6
N.A.
7
N.A.
8
ZS
9
ZS (SOTF)
10
ZG
11
ZG (SOTF)
12
DISCAR
13
DEFCAR
14
N.A.
15
SOTF-OC
16
STUB-OC
17
OC
18
EF
19
OCN
20
UC
21
THM
22
BCD
23
N.A.
24
OV
25
OVS
26
OVG
27
N.A.
28
N.A.
29
UV
30
UVS
31
N.A.
32
FRQ
33
DFRQ
34
N.A.
35
N.A.
36
N.A.
37
N.A.
38
N.A.
39
N.A.
40
Note: 'N.A.' represents 'Not available for the IED', 'X' represents a 'Valid signal received
from the protection function', '–' represents that no 'valid signal' received in the
Trip and ARC-block signals provided by the protection functions
FC*_OPT
_TRIP-B
X
X
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
X
X
X
X
X
X
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
- 408 -
'). Note that an operation block
*
FC*_OPT
FC*_OPT
_TRIP-C
_TRIP
X
X
X
X
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
X
X
X
X
X
X
N.A.
N.A.
X
X
X
X
X
X
X
X
N.A.
N.A.
X
X
X
N.A.
N.A.
N.A.
N.A.
X
X
N.A.
N.A.
X
X
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
6F2S1914 (0.49)
FC*_OPT_ARC-
Note
BLOCK
X
X
X
X
N.A.
N.A.
N.A.
N.A.
X
X
X
X
X
N.A.
X
X
X
X
X
X
X
X
N.A.
X
X
X
N.A.
N.A.
X
X
N.A.
X
X
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
GRL200 (Soft 033 & 037)