Current Derating Depending On The Pulse Frequency, 200 V Inverters - Siemens SINAMICS G12 Hardware Installation Manual

Pm240-2 power modules, ip20 / push-through technology (pt)
Table of Contents

Advertisement

7.5.3

Current derating depending on the pulse frequency, 200 V inverters

Article number
Pulse frequency [kHz]
6SL3210-1PB13-0 . L0
6SL321 . -1PB13-8 . L0
6SL3211-1PB15-5 . L0
6SL3210-1PB17-4 . L0
6SL321 . -1PB21-0 . L0
6SL3210-1PB21-4 . L0
6SL321 . -1PB21-8 . L0
6SL3210-1PC22-2 . L0
6SL3210-1PC22-8 . L0
6SL3210-1PC24-2 . L0
6SL3210-1PC25-4 . L0
6SL321 . -1PC26-8 . L0
6SL3210-1PC28-0 . L0
6SL321 . -1PC31-1 . L0
6SL3210-1PC31-3 . L0
6SL3210-1PC31-6 . L0
6SL321 . -1PC31-8 . L0
*) Factory setting
The permissible motor cable length depends on the particular cable type and the pulse frequency that
has been selected
Power Module PM240-2
Hardware Installation Manual, 08/2017, A5E33294624B AG
LO
power
[kW]
2
4
*)
0.55
3.2
3.2
0.75
4.2
4.2
1.1
6
6
1.5
7.4
7.4
2.2
10.4
10.4
3
13.6
13.6
4
17.5
17.5
5.5
22
22
7.5
28
28
11
42
42
15
54
54
18.5
68
68
22
80
80
30
104
104
37
130
130
45
154
154
55
178
178
7.5 Technical data, 200 V inverters
LO base load output current [A]
6
8
10
2.7
2.2
1.9
3.6
2.9
2.5
5.1
4.2
3.6
6.3
5.2
4.4
8.8
7.3
6.2
11.6
9.5
8.2
14.9
12.3
10.5
18.7
15.4
13.2
23.8
19.6
16.8
35.7
29.4
25.2
45.9
37.8
32.4
57.8
47.6
40.8
68
56
48
88.4
72.8
62.4
110.5
91
---
130.9
107.8
---
151.3
124.6
---
Technical data
12
14
16
1.6
1.4
1.3
2.1
1.9
1.7
3
2.7
2.4
3.7
3.3
3
5.2
4.7
4.2
6.8
6.1
5.4
8.8
7.9
7
11
9.9
8.8
14
12.6
11.2
21
18.9
16.8
27
24.3
21.6
34
30.6
27.2
40
36
32
52
46.8
41.6
---
---
---
---
---
---
---
---
---
89

Hide quick links:

Advertisement

Table of Contents
loading