3.5

Commissioning

SICAM FSI V2.0 B-Sensor Commissioning

3.5.1
Visual indication for voltage presence on a line will be seen only once when the device has been mounted on
the line after it has been magnetically reset. Magnetic reset can be done by touching the magnet adaptor to
the device transparent cover for approximately 1 s. The reset can also be done once the device is mounted on
the line.
The device detects the MV overhead line voltage first time after magnetic reset and confirms by flashing all
the board LEDs in sequence 10 times.
Commissioning SICAM FSI B-Sensor using Magnet Adaptor
To commission the SICAM FSI, proceed as follows:
Reset the device by touching the magnet adaptor (MLFB: 6MD2318 - 4MA04) to the device transparent
cover for approximately 1 s.
Board LEDs flash 10 times to confirm that the device is healthy and ready for operation.
[le_fsi_magnetreset, 1, en_US]
Figure 3-28
(1)
Transparent cover
(2)
Magnet adaptor
(3)
Hot stick with shot gun
SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual
E50417-H8940-C656-A1, Edition 08.2023
Reseting the Device using Magnet Adaptor using Hot Stick with Shot Gun