Emi/Emc Tests - Siemens SICAM V01.00 Manual

Fault sensor indicator v2.0 b-sensor
Table of Contents

Advertisement

Type Testing

7.1 EMI/EMC Tests

7.1
EMI/EMC Tests
Table 7-1
Test
Electrostatic discharge test
Power frequency magnetic
field immunity 50 Hz/60 Hz
Pulse magnetic field immunity IEC 62689-1, Table 16
Radiated emission test
Damped oscillatory magnetic
field test
Radio frequency, electromag-
netic field immunity
110
EMI/EMC Tests
Reference Standard
IEC 62689-1, Table 16
IEC 61000-4-2
IEC 61326-1
IEC 62689-1, Table 16
IEC 61000-4-8
IEC 61326-1
IEC 61000-4-9
IEC 61326-1
CISPR 32
EN 55032
IEC 61326-1
IEC 62689-1
IEC 61000-4-10
IEC 62689-1
IEC 61000-4-3
IEC 61326-1
Test Requirement
Severity class 3
6 kV contact discharge, 8 kV air
discharge
Severity class 4
30 A/m continuous, 300 A/m for 1 s to
3 s
As per IEC 61326; 30 A/m 50 Hz, 60 Hz
(magnetically sensitive equipment)
Severity class 4
300 A/m peak value; 20 positive and
20 negative
Class A
30 MHz to 1000 MHz
(30 MHz to 230 MHz): 40 dB (µV/m) QP
(at 10 m)
(230 MHz to 1000 MHz): 47 dB (µV/m)
QP (at 10 m)
1 GHz to 6 GHz
(1 GHz to 3 GHz): 56 dB (µV/m) AV,
76 dB (µV/m) PK (at 3 m)
(3 GHz to 6 GHz): 60 dB (µV/m) AV,
80 dB (µV/m) PK (at 3 m)
Severity class 4,
30-A/m peak value
Oscillation frequency: 0.1 MHz and
1 MHz, ± 10%
Orientation: XYZ
Test duration: 2 s or continuous for
1 min
Severity class 3
0.08 GHz to 1 GHz
10 V/m, 80% AM 1 kHz, 1 % step
1 GHz to 6 GHz
3 V/m, 80 % AM 1 kHz, 1 % step
Dwell time: 2.85 s
SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual
E50417-H8940-C656-A1, Edition 08.2023

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents