Device Functions
4.6 Inrush Restraint
4.6
Inrush Restraint
During the voltage restoration on the MV overhead line, the device blocks the detection of faults due to the
transformer magnetization within the configured inrush-restraint time.
The inrush-restraint time can be configured as Disabled, 3 s, 30 s, and 60 s. The inrush-restraint time is
initiated only after a voltage is detected in SICAM FSI.
If the inrush-restraint time is set as Disabled, it is internally considered as 1 s.
[dw_sfsi_inrushrestraint, 1, en_US]
Figure 4-6
62
Inrush Restraint
SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual
E50417-H8940-C656-A1, Edition 08.2023