Thrust the device against the MV overhead line until the mounting clamps snaps to the MV overhead
line.
In order to confirm the proper snapping of the clamps, exert a slight pull to the device on the MV
overhead line. The device must withstand the specified pulling motion without any signs of loosening or
displacement from the MV overhead line.
The firm positioning of the device on the MV overhead line when subjected to pulling force will confirm
the secure mounting of the device.
[dw_fsi_devpull-20160620, 1, en_US]
Figure 3-10
To lower the hot stick with shotgun from the MV overhead line. Open the jaw hook of the hot stick with
shotgun, refer to
[dw_sfsi_hotstckshotgun, 1, --_--]
Figure 3-11
NOTE
i
i
Before the hot stick with shotgun is lowered, the orientation of SICAM FSI must be aligned as shown in
Figure 3-11
and ensure that device transparent cover is always facing towards the ground.
SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual
E50417-H8940-C656-A1, Edition 08.2023
Device Secured on the MV Overhead Line
Figure
3-6. Once, the hook is open, lower the hot stick with shotgun.
Lowering Hot Stick with Shot Gun
Getting Started
3.4 SICAM FSI Mounting
31