Electrical Tests - Siemens SICAM V01.00 Manual

Fault sensor indicator v2.0 b-sensor
Table of Contents

Advertisement

7.4

Electrical Tests

Table 7-4
Test
Dielectric withstand
Overvoltage
Degree of pollution
Maximum altitude above sea level
Short-circuit current withstand test IEC 62689-1
Short time current/Dynamic test
Switching impulse test
Lightning impulse test
SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual
E50417-H8940-C656-A1, Edition 08.2023
Electrical Tests
Reference Standard
IEC/EN 61010-1
IEC/EN 61010-1
IEC/EN 61010-1
IEC/EN 61010-1
IEEE495
IEC 60060-1
IEC 60060-1
Type Testing
7.4 Electrical Tests
Test Requirement
125 kV with the help of hotstick
Category IV
Category 2
5000 m
12.5 kA @ 1 s and 31.25 kA peak
25 kA @ 170 ms and 62.5 kA peak
25 kA RMS for 3 s and 62.5 kA peak
40 kA RMS for 1 s and 100 kA peak
250 kV peak
2500 µs, no of shots: 5
350 kV peak
50 µs, no of shots: 5
113