Grounding wiring
Example usage of FX
Ethernet
modular jack
(RJ45)
FX
Applicable cables
Electric wire size
0.5 to 1.5 mm
• When using a stranded cable or solid cable as it is
- Twist the end of the stranded cable so that loose wires will not stick out.
- Do not solder-plate the end of the cable.
5.2

Screw Size and Tightening Torque

The grounding terminal of the Ethernet adapter is a M2.5 screw.
Set the tightening torque to 0.4 to 0.5 N·m.
Terminal screws must be secured to prevent a loose connection thus avoiding a malfunction.
Failure to do so may cause equipment failures or malfunctions.
Caution
When tightening a grounding terminal, use a screwdriver suitable for the terminal screw. The screwdriver
which does not suit the thread groove is used, tightening torque will not be able to be achieved. To achieve
the appropriate tightening torque shown in the above, use the following screwdriver or an appropriate
replacement.
<Reference>
Manufacturer
Weidmuller Interface GmbH & Co. KG
Weidmuller Interface GmbH & Co. KG
30
3U
D Grounding
(100Ω or less)
FX
3U
-ENET-ADP
3U
2
(AWG 20 to 16)
Approx. 8 mm
(0.31")
SD 0.6 3.5 100
Model name
SDIK PH0
5.2 Screw Size and Tightening Torque
Model number
9008560000
9008330000
5 Wiring