11. Control & Status Registers
11.1. Control Registers
When controlling the drive through any fieldbus network it is recommended to use the registers below. These registers support the Modbus
RTU Function Code Write Multiple Registers and so all registers can be set in a single transaction greatly speeding up the drive control.
These registers are pre-mapped to the CAN RX PDO1 and are also used in the EDS file for Ethernet/IP communication.
The functions are described more fully in section 1 1.2. Standard Status Registers on page 55.
Modbus
Name
RTU
Register
PDO0
1
PDO1
2
PDO2
PDO2
PDO2
PDO2
PDO2
PDO2
PDO2
PDO2
PDO2
PDO2
PDO2
3
3
3
3
3
3
3
3
3
3
3
PDO3
PDO3
PDO3
PDO3
PDO3
PDO3
PDO3
PDO3
PDO3
4
4
4
4
4
4
4
4
4
11.1.1. Drive Control Word PDO0
11.1.1. Drive Control Word PDO0
Bit
Bit
Bit
Bit
Function When "0"
Function When "0"
Function When "0"
Function When "0"
15
15
14
14
13
13
12
12
1 1
10
10
9
9
9
Digital output OFF
Digital output OFF
Digital output OFF
8
8
8
Relay Output OFF
Relay Output OFF
Relay Output OFF
7
6
5
4
3
3
3
Operation Permitted
Operation Permitted
Operation Permitted
2
No Action
No Action
1
1
1
Operation Permitted
Operation Permitted
Operation Permitted
0
For normal operation, Bit 3 has the highest priority, bit 0 has the lowest priority (bit 3>bit 1>bit 0).
For normal operation, Bit 3 has the highest priority, bit 0 has the lowest priority (bit 3>bit 1>bit 0).
Note that the Run / Stop (bit 0), Fast Stop (bit 1) and Coast Stop (bit 3) only operate under the following conditions:
Note that the Run / Stop (bit 0), Fast Stop (bit 1) and Coast Stop (bit 3) only operate under the following conditions:
Fieldbus control (or CAN) is selected in P-12
Fieldbus control (or CAN) is selected in P-12
P-31= 0 or 1
P-31= 0 or 1
Otherwise, Run / Stop function is controlled by drive control terminals.
Reset function (bit 2) is always active when the drive operates in Fieldbus or CAN mode.
Bits 8 and 9 may optionally be used to control the state of the built in Analog Output in Digital Mode and the Output relay. This
function is activated if selected by the relevant parameter:
Relay Output P-18
Digital Output, P-25
Refer to the programming Guide for further information.
11.1.2. Frequency Setpoint PDO1
Frequency Setpoint value is transferred with one decimal place (200 = 20.0Hz).
The maximum value is limited by P-01.
Sending a value that exceeds P-01 will result in an Exception error.
11
54 | Fieldbus Guide | Version 1.02
CAN
Sub
PDO
Parameter
Open
Index
Map
Number
Index
2000h
0
Y
2001h
0
Y
2002h
2002h
2002h
2002h
2002h
2002h
2002h
2002h
2002h
2002h
2002h
0
0
0
0
0
0
0
0
0
0
0
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
2003h
2003h
2003h
2003h
2003h
2003h
2003h
2003h
2003h
0
0
0
0
0
0
0
0
0
Y
Y
Y
Y
Y
Y
Y
Y
Y
Function When "1"
Function When "1"
Function When "1"
Function When "1"
No Function Assigned
No Function Assigned
Digital Output ON
Digital Output ON
Relay Output ON
Relay Output ON
No Function Assigned
No Function Assigned
Coast Stop
Coast Stop
Reset Active Fault
Reset Active Fault
Fast Stop
Fast Stop
Stop
Stop
Run
Run
Upper
Lower
Byte
Byte
-
Control Word
-
Frequency Setpoint
-
-
-
-
-
-
-
-
-
-
-
PID Setpoint, Analog Output
PID Setpoint, Analog Output
PID Setpoint, Analog Output
PID Setpoint, Analog Output
PID Setpoint, Analog Output
PID Setpoint, Analog Output
PID Setpoint, Analog Output
PID Setpoint, Analog Output
PID Setpoint, Analog Output
PID Setpoint, Analog Output
PID Setpoint, Analog Output
-
-
-
-
-
-
-
-
-
Ramp Time
Ramp Time
Ramp Time
Ramp Time
Ramp Time
Ramp Time
Ramp Time
Ramp Time
Ramp Time
Format
Type
Scaling
WORD
R/W
See Below
S16
R/W
1dp, e.g. 100 = 10.0Hz
-
-
-
-
-
-
-
-
-
-
-
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
0 – 4096 = 0 – 100%
0 – 4096 = 0 – 100%
0 – 4096 = 0 – 100%
0 – 4096 = 0 – 100%
0 – 4096 = 0 – 100%
0 – 4096 = 0 – 100%
0 – 4096 = 0 – 100%
0 – 4096 = 0 – 100%
0 – 4096 = 0 – 100%
0 – 4096 = 0 – 100%
0 – 4096 = 0 – 100%
U16
U16
R/W
R/W
R/W
2dp, e.g. 500 = 5.00s
2dp, e.g. 500 = 5.00s
2dp, e.g. 500 = 5.00s
www.invertekdrives.com
Need help?
Do you have a question about the Optidrive E3 ODE-3 Series and is the answer not in the manual?
Questions and answers