10.7.2. Profibus Master Configuration
The latest applicable GSD file may be downloaded from the HMS website, www.anybus.com.
The actual configuration process will differ for different Profibus Master Systems and is not possible to explain in this document.
Example configurations for Siemens PLC are provided on the HMS website.
When configuring the communication between the Master System and the gateway, 4 words of Input Process Data and 4 words
of Output Process Data should be allocated per drive connected the gateway, up to a maximum of 32 Input and Output words. If
necessary, a configuration may be chosen in the Profibus Master which supports more than the connected number of drives, e.g. if 3
drives are connected to the gateway, the Master System can be configured for 12, 16 or even 32 words of Input and Output process
data. The additional words will simply not contain any data.
10.8. DeviceNet Gateway Features – OD-DEVNT-IN
Communications Adapter, profile no. 12
Group two server
Mac ID and baud rate configuration via on-board switches
Polled, Change-of-state and Bit strobed I/O
olled, Change-of-state and Bit strobed I/O
10.8.1. Installation
10.8.1. Installation
10.8.1.1. Overview - Module Front
10.8.1.1. Overview - Module Front
Configuration Switches
Configuration Switches
Mac ID
Mac ID
Baud rate
Baud rate
10.8.1.2. Configuration Switches – Baud Rate
Switch 1
Switch 2
OFF
OFF
ON
ON
10
52 | Fieldbus Guide | Version 1.02
1
1
LED Indicators
LED Indicators
1
1
2
2
2
2
3
3
4
4
5
5
6
6
3
3
4
4
5
5
6
6
Baud Rate
OFF
125k
ON
250k
OFF
500k
ON
N/A
Network
Network
Off
Off
Status
Status
Green
Green
Flashing Green
Flashing Green
Red
Red
Flashing Red
Flashing Red
Module
Module
Off
Off
Status
Status
Green
Green
Flashing Green
Flashing Green
Red
Red
Flashing Red
Flashing Red
Not Used
Not Used
Not Used
-
-
-
Not Used
Not Used
Not Used
-
-
-
Fieldbus
Fieldbus
Flashing Green
Flashing Green
Diagnostics
Diagnostics
Green
Green
Red
Red
Device Status Off
Device Status Off
Device Status Off
Alternating Red / Green
Alternating Red / Green
Alternating Red / Green
Green
Green
Flashing Green
Flashing Green
Red
Red
Flashing Red
Not online
Not online
Link ok, online, connected
Link ok, online, connected
Online, not connected
Online, not connected
Critical link failure
Critical link failure
Connection timeout
Connection timeout
No power
No power
Device operational
Device operational
Data size bigger than configured
Data size bigger than configured
Unrecoverable fault
Unrecoverable fault
Minor fault
Minor fault
-
-
-
-
Running, but one or more transaction errors
Running, but one or more transaction errors
Running
Running
Transaction error / subnet stopped
Transaction error / subnet stopped
Power Off
Power Off
Invalid / missing configuration
Invalid / missing configuration
Invalid / missing configuration
Initialising
Initialising
Running
Running
Bootloader Mode
Bootloader Mode
Diagnostic Code
www.invertekdrives.com
Need help?
Do you have a question about the Optidrive E3 ODE-3 Series and is the answer not in the manual?
Questions and answers