4 -OPERATION
4.2.2 - Operating modes
The user can normally choose one of three available operating
modes, i.e. cooling, heating or domestic hot water production only. 
Other modes such as booster cooling or booster heating, purge, 
and drying, can be selected only with service access level.
The unit may run in the following modes:
■ Off: Unit is requested to stop.
■ Cool: Unit is requested to run in Cooling mode.
■ Heat: Unit is requested to run in Heating mode.
■ DHW Only: Unit is requested to run in DHW mode Only.
■ Booster Cool: Unit is requested to run in Cooling mode at
maximum compressor frequency.
■ Booster Heat:  Unit is requested to run in Heating mode at
increased compressor frequency.
■ Purge:  Water pump is requested to run in order to purge the
hydraulic circuit.
When  Cooling  mode  is  selected,  the  chiller  or  heat  pump  will 
operate in the Cooling mode in order to cool the water loop to the 
selected temperature.
When the heat pump is in Heating mode, the heat pump heats 
the water loop to the selected temperature. When the outdoor air 
temperature is very low, electric heaters or boiler heating can be 
used in order to satisfy the heating demand.
When DHW Only is requested, the unit is not allowed to operate 
in cooling or heating modes.
It  is  also  possible  for  the  unit  to  operate  in  DHW  mode  when 
heating mode or cooling mode is selected, according to schedule 
/ temperature condition / maximum runtime.
When the system is in the Off mode, the compressor and the pump 
are  stopped  (except  for  home  anti-freeze  protection  and  water 
freeze protection, refer to § 4.2.6 Home anti-freeze protection and 
4.2.7 Water freeze protection).
4.2.3 - Operating mode control
The  operating  mode  selection  may  differ  depending  on  access 
level  and  the  use  of  communication  methods,  i.e.  WUI  display, 
Proprietary Protocol communication, or JBus communication. 
In the following sections of this document,the configuration steps 
are the same for all of these three communication methods, except 
when the configuration is described with WUI direct access.
a - WUI control
If the unit is fitted with a user interface, the mode selection can be 
done by direct access on WUI.
When  the  unit  is  Off,  press  the  Mode  key  to  wake  up  the  user 
interface and then press the Mode key successively to select the
required operating mode.

Table 4: Different operating modes

System Mode
Off
Cool
Heat
DHW only
Booster Cool
(1)
Booster Heat
(1)
Purge
(1)
Drying
(1)
(1)  Service access level only (with password 0120).
For more information on user interface, please refer to the WUI 
end user manual.
WUI display
Icon
-
[no icon]
[steady icon]
[steady icon]
[steady icon]
[flashing fast]
[flashing fast]
[flashing fast]
[flashing slow]
49