Water Connections - Riello NXHP Series Installation, Operation And Maintenance Instructions

Table of Contents

Advertisement

2 - INSTALLATION OF UNIT
2.2.4 - Checks before system start-up
Before  the  start-up  of  the  refrigeration  system,  the  complete 
installation,  including  the  refrigeration  system  must  be  verified 
against the installation drawings, dimensional drawings, system 
piping and instrumentation diagrams, and wiring diagrams.
For these checks national regulations must be followed.
External visual installation checks:
■ Ensure that the machine is charged with refrigerant. Verify on 
the unit nameplate that the 'fluid being transported' is R-290 
and is not nitrogen.
■ Compare the complete installation with the refrigeration system 
and power circuit diag rams.
■ Check that all components comply with the design specifications.
■ Check that all protection documents and equipment provided
by the manufacturer (dimensional drawings, P&ID, declarations 
etc.) to comply with the regulations are present.
■ Verify that the environmental safety and protection and devices
and arrangements provided by the manufacturer to comply with 
the regulations are in place.
■ Verify that all documents for pressure containers, certificates, 
name  plates,  files,  instruction  manuals  provided  by  the 
manufacturer to comply with the regulations are present.
■ Verify the free passage of access and safety routes.
■ Verify the instructions and directives to prevent the deliberate
removal of refrigerant gases.
■ Verify the installation of connections.
■ Verify the supports and fixing elements (materials, routing and 
connection).
■ Verify the quality of welds and other joints.
■ Check the protection against mechanical damage.
■ Check the protection against heat.
■ Check the protection of moving parts.
■ Verify the accessibility for maintenance or repair and to check
the piping.
■ Verify the status of the valves.
■ Verify the quality of the thermal insulation and of the vapour
barriers.

2.3 - Water connections

For size and position of the unit water inlet and outlet connections 
refer to the certified dimensional drawings supplied with the unit. 
The water pipes must not transmit any radial or axial force to the 
heat exchangers nor any vibration.
The use of flexible tubing is mandatory to limit the forces applied 
to the heat exchanger connectors.
The  water  supply  must  be  analysed  and  appropriate  filtering, 
treatment, control devices, shut-off and bleed valves and circuits 
built in, to prevent corrosion (example: damage to the protection 
of the tube surface if the fluid is polluted), fouling and deterioration 
of the pump fittings.
Before any start-up verify that the heat exchange fluid is compatible 
with the materials and the water circuit coating.
In case additives or other fluids than those recommended by the 
manufacturer are used, ensure that the fluids are not considered 
as a gas.
Recommendations on heat exchange fluids:
■ No NH
 ammonium ions in the water, they are very detrimental for 
4+
copper. This is one of the most important factors for the operating
life of copper piping. A content of several tenths of mg/l will badly 
corrode the copper over time.
■ Cl
-
  Chloride  ions  are  detrimental  for  copper  with  a  risk  of 
perforations by corrosion by puncture. If possible keep below 
10 mg/l.
■ SO
sulphate  ions  can  cause  perforating  corrosion,  if  their 
2-
4
content is above 30 mg/l.
■ No fluoride ions (<0.1 mg/l).
■ No Fe
and Fe
  ions  with  non  negligible  levels  of  dissolved 
2+
3+
oxygen must be present. Dissolved iron < 5 mg/l with dissolved 
oxygen < 5 mg/l.
■ Dissolved silicon: silicon is an acid element of water and can 
also lead to corrosion risks. Content < 1mg/l.
■ Water  hardness:  >0.5  mmol/l.  Values  between  1  and  2.5 
mmol/l can be recommended. This will facilitate scale deposit 
that can limit corrosion of copper. Values that are too high can
cause piping blockage over time. A total alkalimetric title (TAC) 
below 100 mg/l is desirable.
■ Dissolved oxygen: Any sudden change in water oxygenation 
conditions must be avoided. It is as detrimental to deoxygenate
the water by mixing it with inert gas as it is to over-oxygenate 
it  by  mixing  it  with  pure  oxygen.  The  disturbance  of  the 
oxygenation conditions encourages destabilisation of copper
hydroxides and enlargement of particles.
■ Electric conductivity: 0.001-0.06 S/m (10-600 µS/cm).
■ pH: Ideal case pH neutral at 20-25°C (7 < pH < 8).
CAUTION:
Charging, adding or draining fluid from the water circuit must
be done by qualified personnel, using air vents and materials
suitable for the products. Water circuit charging devices are
field-supplied.
The installation of an automatic air vent on the water loop
leaving the unit is mandatory. This air vent must be situated
on a well ventilated area without ignition source.
Charging and removing heat exchange fluids should be done
with devices that must be included on the water circuit by the
installer. Never use the unit heat exchangers to add heat
exchange fluid.
CAUTION:
The use of units in an open water loop is forbidden. Do not
use the water loop of the unit to heat directly the pool water.
Use a well design water echanger and all the safety component
necessary on the pool system.
2.3.1 - Operating precautions and recommendations
The water circuit should be designed to have the least number of 
elbows and horizontal pipe runs at different levels. Below the main 
points to be checked for the connection:
■ Comply with the water inlet and outlet connections shown on 
the unit.
■ Install manual or automatic air purge valves at all high points
in the circuit.
■ All purges must be installed in an igntion source free
environment.
■ Make sure that no water above 75 °C can enter the unit water 
circuit at any time during operation or maintenance.
■ Use a pressure reducer to maintain pressure in the circuit(s) 
and install a relief valve as well as an expansion tank. Units 
include a relief valve.
■ Install  drain  connections  at  all  low  points  to  allow  the  whole 
circuit to be drained.
■ Install  stop  valves,  close  to  the  entering  and  leaving  water 
connections.
■ Use flexible connections to reduce vibration transmission.
■ Insulate  all  pipework,  after  testing  for  leaks,  both  to  reduce 
thermal leaks and to prevent condensation.
■ Use thermal tape to seal joints and to seam the insulation.
23

Advertisement

Table of Contents
loading

Table of Contents