2 - INSTALLATION OF UNIT
CAUTION:
Before lifting the unit, check that all casing panels are securely fixed in place. Lift and set down the unit with great care.
Tilting and jarring can damage the unit and impair unit operation.
If NXHP units are hoisted with rigging, it is advisable to protect coils against crushing while a unit is being moved. Use struts or a lifting 
beam to spread the slings above the unit. Do not tilt a unit more than 15°.
CAUTION:
Never push or lever on any of the enclosure panels of the unit. Only the base of the unit frame is designed to withstand such
stresses.
2.2.3 - Removing the unit panel
To access at the inside of the unit (refrigerant parts / electrical parts), the panel can be removed. This operation must be carried out 
by a qualified technician.
It is advised to conduct a leak detection before opening any panel. In the technician is not qualified to conduct this leak detection, any 
ignition source must be eliminated in the area within two (2) meters of the unit. When the panel is opened, wait for five (5) minutes 
before doing any intervention inside the unit.

Figure 4 : How to remove front panel for 4 to 10 units