6 - ALARM DESCRIPTION

6.1 - Alarm listing

The following tables of alarms list their probable cause and the likely effect on the unit, as well as the reset type. Proposed investigations 
and corrective actions shall be performed by fully qualified technician.
Description
1
EWT sensor failure
LWT sensor failure
2
Refrigerant Temperature (TR) sensor 
3
failure
4
OAT sensor failure
DHW_TT sensor failure
5
6
CHWSTEMP sensor failure
10
Discharge Temperature (TD) sensor failure
Air Exchanger Temperature (TE) sensor 
11
failure
Suction Temperature (TS) Sensor failure
14
TE & TS sensors wrongly connected or 
16
PMV failure
Suction Pressure transducer failure
17
20
Loss of communication with UI
Loss of communication with Inverter
21
23
Loss of communication with Slaves
Loss of communication with Master
24
Loss of communication with Jbus Master
25
31
Safety Input
32
Flow Switch failure
33
High Pressure Switch failure
Leak detection alarm
40
41
Low Superheat failure
Compressor not started
42
43
Drive unconfigured
44
Four-way Valve failure
45
Lower Fan not started
Upper Fan not started
46
66

Table 6: Alarms listing

Reset type
When value returns within correct 
Continue X
range
When value returns within correct 
Stop
X
range
When value returns within correct 
Cpr stop X
range
When value returns within correct 
Continue X
range
DHW
When value returns within correct 
X
Failed
range
When value returns within correct 
X
range
X Error becomes definite after 
Stop
X
retrying operation for 4 times.
 Error becomes definite after 
Stop
X
X
retrying operationfor 4 times.
Error becomes definite after 
Stop
X
X
retrying operation for 4 times.
X Error becomes definite after 
Stop
X
retrying operation for 4 times.
X Error becomes definite after 
Stop
X
retrying operation for 4 times.
When a new message is 
Continue X
received from the UI
When a new message is 
Stop
X
received from the Inverter
Master
X
continues
Stop
X
When a new valid message is 
Stop
X
received from the Jbus Master
Stop
X
When Safety Input is closed
X Error becomes definite after 
Stop
retrying operation for 5 times.
Error becomes definite after 
Stop
X
retrying operation for 3 times.
When value returns within correct 
X
range
When value returns within correct 
Stop
X
range
Stop
X
Stop
X
Drive configuration completed
When value returns within correct 
Stop
X
range
Power cycle after more than 5 
Stop
X
occurrences in 1 hour
Power cycle after more than 5 
Stop
X
occurrences in 1 hour
Investigation / corrective actions
Comment
1. Check EWT sensor (EWT).
2. Check NHC board.
1. Check LWT sensor (LWT).
2. Check NHC board.
1. Check TR sensor (TR).
2. Check NHC board.
1. Check Additional OAT sensor (OAT).
2. Check NHC board.
1. Check DHW sensor (DHW_TT).
2. Check NHC board.
1. Check CHWSTEMP sensor
(CHWSTEMP).
2. Check NHC board.
1. Check discharge temp. sensor (TD).
2. Check inverter connection
1. Check temp. sensor (TE).
1. Check suction temp. sensor (TS).
1. Check temp. sensor (TE, TS)
2. Check PMV (expansion valve) 
electrical connexion
1. Check suction pressure. sensor (PS).
1. Ensure that water flow rate is 
sufficient and fan operation is normal
2. Check PMV operation
3. Check high pressure switch electrical 
connection
1. Stop and disconnect the unit
2. Check compressor connection
1. Check operation of 4-way valve
2. Check 4-way valve coil and 
connection
3. Check TE, TS, TR, EWT and OAT 
sensors
1. Stop and disconnect the unit
2. Check fan motor connection
3. Check if impeller is not blocked
1. Stop and disconnect the unit
2. Check fan motor connection
3. Check if impeller is not blocked