Setting The T/H Sensor - Huawei UPS5000-H-600 User Manual

Hide thumbs Also See for UPS5000-H-600:
Table of Contents

Advertisement

UPS5000-H-600 kVA-FTN
User Manual (Singapore, 100 kVA Power Modules)
Figure 5-3 BCB connection settings
----End

5.1.5.2 Setting the T/H Sensor

Context
The ambient T/H sensor has been installed by referring to the installation section.
The ambient T/H sensor can also be used as a battery temperature sensor. The
monitoring module distinguishes these two types of sensors through their DIP
switch settings.
Procedure
Step 1 Set the DIP switch.
Figure 5-4 DIP switch
Each ambient T/H sensor has a unique DIP switch address, ranging from 32 to 44.
A DIP switch has six binary toggle switches. The bit on the leftmost is the most
significant bit, and the bit on the rightmost is the least significant bit. Bit 1
indicates ON, and bit 0 indicates OFF.
Issue 02 (2023-11-07)
NO TE
● The device address is set in binary mode. 1 is the least significant bit, and 6 is the most
significant bit. ON indicates 1, and OFF indicates 0. The address range is 1 to 63.
● DIP switches 1–6 are used to set the device address, DIP switch 7 is reserved, and DIP
switch 8 is used to switch the temperature display mode.
DIP switch settings on ambient T/H sensors
Copyright © Huawei Digital Power Technologies Co., Ltd.