Setting The T/H Sensor - Huawei UPS5000-H-600 kVA-FTN Quick Manual

Table of Contents

Advertisement

UPS5000-H-600 kVA-FTN
Quick Guide (Singapore, 100 kVA Power Modules)
Figure 2-3 BCB connection settings
----End

2.1.5.2 Setting the T/H Sensor

Context
The ambient T/H sensor has been installed by referring to the installation section.
The ambient T/H sensor can also be used as a battery temperature sensor. The
monitoring module distinguishes these two types of sensors through their DIP
switch settings.
Procedure
Step 1 Set the DIP switch.
Figure 2-4 DIP switch
(1) DIP switch
Issue 01 (2022-11-18)
NO TE
The RS485_R DIP switch is used to enable a build-out resistor so that the ambient T/H
sensor can communicate with the controller. If there are no more than four ambient T/H
sensors on the bus, the RS485_R DIP switch does not need to be set. If there are more than
four, flip the RS485_R DIP switch of the ambient T/H sensor furthest from the UPS to ON.
Copyright © Huawei Digital Power Technologies Co., Ltd.
2 Single UPS Commissioning
63