4.3 (Optional) Setting the BSC Mode

Step 1 Choose System Info > Settings > System Settings and set BSC mode to
Standard BSC.
Figure 4-2 Standard BSC mode
Step 2 Set the BSC master system. On the LCD of one UPS, choose System Info >
Settings > System Settings and set BSC master/slave mode to BSC master
system.
Figure 4-3 BSC master system
Step 3 Set the BSC slave system. On the LCD of the other UPS, choose System Info >
Settings > System Settings and set BSC master/slave mode to BSC slave
system.
Issue 01 (2022-09-26)
NO TE
● The default value of BSC mode is Non-BSC. Set it to Standard BSC mode when the
system is a dual-bus system.
● A dual-bus system consists of one master and one slave BSC system. You can specify
one master and one slave BSC system during initial startup and change the settings
under the guidance of maintenance engineers. Set the BSC master and slave systems to
master and slave modes respectively.
● Ensure that the BSC signal cable between the BSC master and slave systems is properly
connected and that BSC-related hardware is properly installed.