Installation Clearance Requirements
Reserve the following clearances around the cabinet to facilitate operations and
ventilation:
Figure 4-1 Space planning for top cabling configuration
If a bottom cabling cabinet is configured, the customer needs to prepare a cable
tray to support cables routed from the top. The distance between the bottom of
the cable tray and the top of the cabinet must be at least 400 mm.
Issue 02 (2023-11-07)
Ensure that the floor or installation support can bear the weight of the UPS,
batteries, and battery racks.
If the UPS is equipped with a top outlet kit, do not install devices that are
easy to swing on the top of the UPS. Otherwise, the devices may fall off.
Reserve a clearance of at least 950 mm from the front of the cabinet for
ventilation and operations.
Reserve a clearance of at least 500 mm from the top of the cabinet for
operations.
Reserve a clearance of at least 500 mm from the rear of the cabinets for
ventilation. If the UPS will be operated from the rear, reserve a clearance of at
least 800 mm for operations.
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installation and Cable Connection