Huawei UPS5000-H-600 User Manual page 140

Hide thumbs Also See for UPS5000-H-600:
Table of Contents

Advertisement

UPS5000-H-600 kVA-FTN
User Manual (Singapore, 100 kVA Power Modules)
Parameter
Peak shaving
charge start time
1/2/3/4/5/6
Peak shaving
charge end time
1/2/3/4/5/6
Electricity price in
discharge period
1/2/3/4/5/6 for
peak shaving
Electricity price in
peak shaving
charge period
1/2/3/4/5/6
Peak shaving
repetition method
Normal backup
time reserved for
peak shaving (min)
Issue 02 (2023-11-07)
Description
Specifies the start time and
end time of battery charge
during off-peak hours.
NOTICE
A maximum of six charge
periods are supported in a day.
The following conditions must
be met. Otherwise, the system
cannot enter the peak shaving
mode.
● The start time of the current
period must be earlier than
the end time.
● The current period must not
overlap with other periods.
Specifies the electricity price
in a discharge period.
NOTE
Electricity price parameters are
not associated with specific
currency units.
Specifies the electricity price
in a charge period.
NOTE
Electricity price parameters are
not associated with specific
currency units.
Specifies whether to enable
the preceding proactive
charge and discharge rules
from Monday to Sunday. If
the default value Disable is
retained, the rules will not be
enabled.
When the battery backup
time decreases to the preset
value, batteries enter the
non-charge and non-
discharge state during a
discharge period, and
batteries are charged
normally during a charge
period. When the battery
backup time is greater than
the preset value, the system
continues to implement peak
shaving based on the preset
rules.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Single UPS Commissioning
Default Value
Value Range
00:00:00
00:00:00–23:59:59
00:00:00
00:00:00–23:59:59
0.000
0.000–100.000
0.000
0.000–100.000
User-defined
User-defined
10
5–600
132